| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
2/0 X 4 WIRES |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (FLOOR: 014) BX CABLE NOT SUPPORTED NEAR PANEL |
RSLV |
12/13/2017 |
12/13/2017 |
03/21/2018 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 014) BEDROOM OUTLET BOX NOT SUPPORTED |
RSLV |
12/13/2017 |
12/13/2017 |
01/11/2018 |
| |
| 003 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 014) OUTLET PLATE MISSING IN HALLWAY |
RSLV |
12/13/2017 |
12/13/2017 |
03/21/2018 |
| |
| 004 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 014) BEDROOM OUTLET/SWITCH BOX NOT SUPPORTED |
RSLV |
12/13/2017 |
12/13/2017 |
01/11/2018 |
| |
| 005 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 014) KO MISSING IN PANEL |
RSLV |
12/13/2017 |
12/13/2017 |
01/11/2018 |
| |
| 006 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER (FLOOR: 014) LIGHT FIXTURE NOT SUPPORTED LIVING ROOM |
RSLV |
12/13/2017 |
12/13/2017 |
01/11/2018 |
| |
| 007 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 014) ALL BATHROOM TOILETS OUTLETS |
RSLV |
12/13/2017 |
12/13/2017 |
03/21/2018 |
| |
| 008 |
(999) |
OTHER (FLOOR: 014) COLLAR BOX NEEDED THOUGH OUT 314 |
RSLV |
12/13/2017 |
12/13/2017 |
03/21/2018 |
| |
| 009 |
(999) |
OTHER (FLOOR: 014) LAUNDRY RM AND ISLAND ON SAME CKT 210.52 B 2 |
RSLV |
12/13/2017 |
12/13/2017 |
01/11/2018 |
| |
| 010 |
(999) |
OTHER (FLOOR: 014) MAIN BREAKER BLANK MISSING 408.7 |
RSLV |
03/21/2018 |
03/21/2018 |
03/27/2018 |
| |
| 011 |
(999) |
OTHER (FLOOR: 014) FEED IN HALL EMT NEEDS STRAP 358.30 |
RSLV |
03/21/2018 |
03/21/2018 |
03/27/2018 |
| |
| 012 |
(999) |
OTHER (BASEMENT) FUSES SIZES TO WIRE USED 110.3 240 |
RSLV |
03/21/2018 |
03/21/2018 |
03/27/2018 |