BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M402538
Premises: 1120 5 AVENUE MANHATTAN BIN: 1047101     Block: 1505   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1120 5 AV Census Tract:   160.01 Health Area:  2820
APT 14B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 93 STREET,    EAST 94 STREET
Status:   C - JOB IS SIGNED OFF 05/08/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/09/2017 11:23 PM
Application Entered:   10/09/2017 Job Start Date:   10/10/2017
Last Change:   05/08/2018 Job End Date:   10/08/2018
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     03/27/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011903 Licensee Name: WIESLAW MAKSIM
Firm: 003541 Firm Name: DENMAR ELECTRIC CORP
Firm Phone: 718-533-6753  Firm Address: 5 PENN PLAZA 19TH FLOOR NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $200.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANOUK MARKOVITS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  2/0 X 4 WIRES
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
014  14B  92  72    15  92             
Buildings Total 92  72    15  92                
Total Units : 271 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/21/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402538
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/13/2017 12/13/2017 CLC V (58) (9)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 01/11/2018 01/12/2018 HRB J Y (55) (0)
INSPECTION COMMENTS: FAILED NOT FINAL COUNTER TOP NEEDS TO BE FINISH BASEBOARD NOT FINISH DRIVERS ARE NOT INSTALLED FOR LIGHTS APT NOT READY FOR FINAL INSPECTION
 
(3) 03/21/2018 03/21/2018 STP V R (35) (3)
INSPECTION COMMENTS: FAIL. MATCH FUSES PER PHASE IN BASEMENT. FEEDER ADDED IN FIELD. OBJECTIONS CERTIFIABLE.
 
(4) 03/27/2018 03/27/2018 PHG C R (20) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M402538
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 014) BX CABLE NOT SUPPORTED NEAR PANEL
RSLV 12/13/2017 12/13/2017 03/21/2018
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 014) BEDROOM OUTLET BOX NOT SUPPORTED
RSLV 12/13/2017 12/13/2017 01/11/2018
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 014) OUTLET PLATE MISSING IN HALLWAY
RSLV 12/13/2017 12/13/2017 03/21/2018
 
004 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 014) BEDROOM OUTLET/SWITCH BOX NOT SUPPORTED
RSLV 12/13/2017 12/13/2017 01/11/2018
 
005 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 014) KO MISSING IN PANEL
RSLV 12/13/2017 12/13/2017 01/11/2018
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(FLOOR: 014) LIGHT FIXTURE NOT SUPPORTED LIVING ROOM
RSLV 12/13/2017 12/13/2017 01/11/2018
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 014) ALL BATHROOM TOILETS OUTLETS
RSLV 12/13/2017 12/13/2017 03/21/2018
 
008 (999) OTHER
(FLOOR: 014) COLLAR BOX NEEDED THOUGH OUT 314
RSLV 12/13/2017 12/13/2017 03/21/2018
 
009 (999) OTHER
(FLOOR: 014) LAUNDRY RM AND ISLAND ON SAME CKT 210.52 B 2
RSLV 12/13/2017 12/13/2017 01/11/2018
 
010 (999) OTHER
(FLOOR: 014) MAIN BREAKER BLANK MISSING 408.7
RSLV 03/21/2018 03/21/2018 03/27/2018
 
011 (999) OTHER
(FLOOR: 014) FEED IN HALL EMT NEEDS STRAP 358.30
RSLV 03/21/2018 03/21/2018 03/27/2018
 
012 (999) OTHER
(BASEMENT) FUSES SIZES TO WIRE USED 110.3 240
RSLV 03/21/2018 03/21/2018 03/27/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.