| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
11 |
6X#6THHN, 5X#2THHN |
| B. Over #2 to 1/0 |
2 |
2X1/0 THHN |
| C. Over 1/0 to 250 MCM |
6 |
2X1/0, 2X3/0, 2X4/0 |
| D. Over 250 MCM |
3 |
2X600MCM, 2X350MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
18 |
7X60A, 4X100A, 1X175A, 6X |
| D. 3 Phase Over 225 AMPS |
5 |
2X400A, 2X800A, 1X600A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
150A, 175A |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
1 |
60A |
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (FLOOR: 002)FLOOR 2 358.30 EMT 2 1/2 INCHES ARE NOT PROPERLY SUPPORTED (GENERATOR ROOM) |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) APP DOES NOT MATCH . ( AMOUNT OF FEEDERS) |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 003 |
(999) |
OTHER (ALL FLOORS)GND AND 2ND FLOOR 110.2(A) MEDICAL GASES ( NEEDS APPROVAL LETTERFOR LUMINARIES AND ELECTRICAL EQUIPMENT INSTALLED INSIDE OF MEDICALGASES) |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 004 |
(999) |
OTHER (ALL FLOORS) ELEVATOR NEEDS FULL INSPECTION ( NO ACCESS) |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 005 |
(255) |
NO FUSE COORDINATION EXISTS (BASEMENT) BSMT AM 240.12 (A) APPROVAL SERVICE FUSE COORDINATION |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 006 |
(999) |
OTHER (BASEMENT)BSMT 250.53 NOT PROVIDED SUPPLEMENTAL ELECTRODE ( SPRINKLER PIPE) |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 007 |
(999) |
OTHER (BASEMENT)BSMT 408 .36 NOT PROVIDED INDIVIDUAL PROTECTION OVER 42 OVERCURRENTDEVICES. ( PANEL : LL-C SEC-1 , LL-C SEC-2/ ELL-CR-V) |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 008 |
(999) |
OTHER (BASEMENT) BSMT DOES NOT FILE FOR ELECTRICAL METER / # 10 WIRE |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 009 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR) CELLAR 408.4 PANEL DIRECTORY INCOMPLETE ( PANEL ELL-CR-ISO) |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 010 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (CELLAR)CELLAR 210.8 NOT PROVIDED GFCI ( JANITOR ROOM/ SURGICAL ATTIRE ROOM) T-OUT |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 011 |
(999) |
OTHER (CELLAR)CELLAR . 110.3 EMERGENCY LUMINARIES BALLAST ARE NOT SUPPORTED (DROP CEILING) |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 012 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (GROUND FLOOR) GND 210.8 NOT PROVIDED GFCI EXAM ROOM. |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 013 |
(999) |
OTHER (GROUND FLOOR)GND 314.20 JUNCTION BOX SET BACK COMBUSTIBLE MATERIAL ( RECEPTIONDESK, WAITING AREA) T-OUT |
OPEN |
06/05/2019 |
06/05/2019 |
|
| |
| 014 |
(999) |
OTHER (GROUND FLOOR)GND 422.52 DRINKING FOUNTAIN OUTLET MUST BE GFCI PROTECTED |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 015 |
(999) |
OTHER (MEZZANINE-ONLY 1 MEZZANINE IN BUILDING)MEZ 110.3 STAIR C , TOP OF STAIR. LUMINARIES COVER , HANGING OUT |
RSLV |
06/05/2019 |
06/05/2019 |
09/06/2019 |
| |
| 016 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ART. 110.16 ARC FLASH LABELS MISSING THROUGHOUT. |
OPEN |
09/06/2019 |
09/06/2019 |
|
| |
| 017 |
(999) |
OTHER (ALL FLOORS)CONTRACTOR NEEDS TO FILE FOR ALL OF THE FEEDERS. OBSERVED 6 SETS600; 6 SETS 350, 2 SETS 4/0-4; 1 SET 3/0-4; 2 SETS 2/0; 4 SETS1/0-4; 4 SETS #2/4; AND 9 SETS #6/4. |
OPEN |
09/06/2019 |
09/06/2019 |
|
| |
| 018 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR)ART. 250.24 THE NEUTRAL IS NOT BONDED IN THE FIRE PUMP SWITCH. |
OPEN |
09/06/2019 |
09/06/2019 |
|
| |
| 019 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (CELLAR) ART. 210.8CR-22& LL SEC1#22 GFCI OUTLET NEEDED |
OPEN |
09/06/2019 |
09/06/2019 |
|