BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M402066
Premises: 225 BOWERY MANHATTAN BIN: 1089461     Block: 426   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 225 BOWERY Census Tract:   36.01 Health Area:  6500
RIVINGTON ST. & PRINCE ST. Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
Related Job Number:    121862751
DOB Cross Street(s):   RIVINGTON STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 04/18/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/27/2017 12:46 PM
Application Entered:   09/27/2017 Job Start Date:   09/27/2017
Last Change:   04/18/2019 Job End Date:   09/27/2019
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     04/18/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $664.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID PAZ
Owner Business Name: AEH-VSLV, LLC
Authorized Representative:  DAVID PAZ
Relationship To Owner:   OWNER REPRESANTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  3  375.00
B. Each Additional 10 Floors Or Less  3  249.00
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/25/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  3 NEW ELEVATORS 15 STOPS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M402066
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/25/2019 03/25/2019 DWB V (70) (4)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(2) 04/18/2019 04/18/2019 PHG C R (60) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M402066
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ROOF) 110.12(A) ELEVATOR DIS SW NOT ACCESSIBLE, SWITCH DOOR JAM.
RSLV 03/25/2019 03/25/2019 04/18/2019
 
002 (302) ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED
(ROOF) 620.81, EMR CONTROLLER NOT PROPERLY BOND, THRU-OUT.
RSLV 03/25/2019 03/25/2019 04/18/2019
 
003 (999) OTHER
(ROOF) 300.50, FMC ENCASE THRU CONCRETE FLOOR, ARE NOT SLEEVE.
RSLV 03/25/2019 03/25/2019 04/18/2019
 
004 (999) OTHER
(ROOF)110.16, ARCH FLASH NOT PROVIDED ELECTRICAL EQUIPMENT, THRU-OUT.
RSLV 03/25/2019 03/25/2019 04/18/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.