BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M401934
Premises: 400 EAST 9 STREET MANHATTAN BIN: 1005862     Block: 436   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 400 E 9TH ST Census Tract:   32 Health Area:  6600
ALL Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):    1 AVENUE,    AVENUE A
Status:   C - JOB IS SIGNED OFF 04/07/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/25/2017 1:10 PM
Application Entered:   09/25/2017 Job Start Date:   09/27/2017
Last Change:   04/07/2018 Job End Date:   02/27/2018
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     04/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $742.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SOL EIFERMAN
Owner Business Name: MATEL REALTY, LLC.
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  (1) 600A (1) 400A
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  3  (1) 500MCM (2) 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  11  SINGLE-PHASE 12-POLE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  (2) THREE-PHASE 24-POLE
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  ALL    20                   
Buildings Total   20                      
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 12 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/25/2017 Notice: 1 - FIRST NOTICE 02/21/2018
Power Issued: 09/25/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACING BASEMENT SERVICE, UPGRADING APT FEEDERS AND RUNNING NEW BRANCH LINES FOR ELECTRIC RANGES IN EACH APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401934
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/09/2018 01/10/2018 EDB V (110) (7)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 02/20/2018 02/21/2018 TOR V Y (80) (2)
INSPECTION COMMENTS: FAIL
 
(3) 03/13/2018 03/13/2018 TOR J Y (35) (0)
INSPECTION COMMENTS: FAIL.
 
(4) 04/04/2018 04/05/2018 AYC C R (65) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M401934
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)EL. STOVE NOT PROPERLY GND 250.118,112,122
RSLV 01/09/2018 01/09/2018 02/20/2018
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS)K/O MISSING IN THE PANELS 110.12
RSLV 01/09/2018 01/09/2018 02/20/2018
 
003 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS)PANELS: AC CABLE MISSING BUSHING 320.40
RSLV 01/09/2018 01/09/2018 02/20/2018
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS) NO AFCI PROTECTION ON NEW WIRING 210.12
RSLV 01/09/2018 01/09/2018 02/20/2018
 
005 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(CELLAR)TEMP. WIRING IN USE 590.3
RSLV 01/09/2018 01/09/2018 02/20/2018
 
006 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
(CELLAR) PANELS : OVER 10 CURRENT CONDUCTORS IN THE RACEWAY310.15B2A
RSLV 01/09/2018 01/09/2018 04/04/2018
 
007 (999) OTHER
(CELLAR) NO ARC FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 01/09/2018 01/09/2018 03/13/2018
 
008 (999) OTHER
(BASEMENT) HANDLE TIE NOT PROVIDED STORE PANELS ART. 210.4
RSLV 02/20/2018 02/20/2018 03/13/2018
 
009 (999) OTHER
(BASEMENT)MAIN WATER GROUND UNDER SIZE AT 800 AMP SERVICE AS PER TABLE 250.66
RSLV 02/20/2018 02/20/2018 03/13/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order