| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
(1) 600A (1) 400A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
3 |
(1) 500MCM (2) 350 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
11 |
SINGLE-PHASE 12-POLE |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
(2) THREE-PHASE 24-POLE |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)EL. STOVE NOT PROPERLY GND 250.118,112,122 |
RSLV |
01/09/2018 |
01/09/2018 |
02/20/2018 |
| |
| 002 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS)K/O MISSING IN THE PANELS 110.12 |
RSLV |
01/09/2018 |
01/09/2018 |
02/20/2018 |
| |
| 003 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ALL FLOORS)PANELS: AC CABLE MISSING BUSHING 320.40 |
RSLV |
01/09/2018 |
01/09/2018 |
02/20/2018 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) NO AFCI PROTECTION ON NEW WIRING 210.12 |
RSLV |
01/09/2018 |
01/09/2018 |
02/20/2018 |
| |
| 005 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (CELLAR)TEMP. WIRING IN USE 590.3 |
RSLV |
01/09/2018 |
01/09/2018 |
02/20/2018 |
| |
| 006 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED (CELLAR) PANELS : OVER 10 CURRENT CONDUCTORS IN THE RACEWAY310.15B2A |
RSLV |
01/09/2018 |
01/09/2018 |
04/04/2018 |
| |
| 007 |
(999) |
OTHER (CELLAR) NO ARC FLASH WARNING ON NEW EQUIPMENT 110.16 |
RSLV |
01/09/2018 |
01/09/2018 |
03/13/2018 |
| |
| 008 |
(999) |
OTHER (BASEMENT) HANDLE TIE NOT PROVIDED STORE PANELS ART. 210.4 |
RSLV |
02/20/2018 |
02/20/2018 |
03/13/2018 |
| |
| 009 |
(999) |
OTHER (BASEMENT)MAIN WATER GROUND UNDER SIZE AT 800 AMP SERVICE AS PER TABLE 250.66 |
RSLV |
02/20/2018 |
02/20/2018 |
03/13/2018 |