| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
2 FLOORS |
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005)EMR-110.2, ELEVATOR MOTOR DIS SW FUSE NOT INSPECT TO CONFORM FUSEW/52.7 AMP AND 40 HP, ID# 50273. |
RSLV |
03/04/2022 |
03/04/2022 |
03/21/2023 |
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005)EMR- 110.16, ARC FLASH LABEL NOT PROVIDED AT NEW ELECTRICAL EQUIPINSTALLED. |
RSLV |
03/04/2022 |
03/04/2022 |
07/26/2023 |
| |
| 003 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS)ART. 240.3, MAIN DISC. SW. FUSES ARE OVER SIZE, USED 125A FUSE,MOTOR 25 HP,460 VOLTS. |
RSLV |
08/10/2022 |
08/10/2022 |
07/26/2023 |
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)ART. 620.53,620.55 ,NOT PROVIDED SIGN TO IDENTIFY THE LOCATION OFTHE SUPPLY SIDE OCPD FOR MAIN SW. DISC. AND CAR LIGHT DISC. SW. IP50411.S |
RSLV |
08/10/2022 |
08/10/2022 |
07/26/2023 |