BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M401688
Premises: 1295 MADISON AVENUE MANHATTAN BIN: 1047067     Block: 1504   Lot: 20
   

DOB NOW: Inspections


Filed: 1295 MADISON AV Census Tract:   160.01 Health Area:  2820
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   EAST 92 STREET,    EAST 93 STREET
Status:   K - CLOSED/CANCELLED 09/10/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/19/2017 3:35 PM
Application Entered:   09/19/2017 Job Start Date:   09/19/2017
Last Change:   09/10/2018 Job End Date:   11/19/2017
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RIVERA, F       On     09/10/2018      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012665 Licensee Name: SHANE R O'CONNOR
Firm: 004502 Firm Name: NTS ELECTRICAL, INC
Firm Phone: 718-429-3234  Firm Address: 37-31 58TH STREET, SUITE B-1 WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $63.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAUL COSTANZA
Owner Business Name: CHARTER COMMUNICATIONS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  30 AMP DISCONNECT
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  2-NO.2 AWG/1-#10 GRND
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/19/2017 Notice: C - CALL TO OFFICE 04/17/2018
Power Issued: 09/19/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401688
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/15/2017 11/15/2017 MLF N (18) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR "WILL RESCHEDULE"
 
(2) 01/11/2018 01/11/2018 EDB V (45) (4)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 04/16/2018 04/17/2018 STP H X (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NEEDS TOOLS FOR INSPECTION
 
(4) 09/10/2018 09/10/2018 FRI K R (5) (0)
INSPECTION COMMENTS: WITHDRAWAL RE; M00047354

OBJECTION FOR APPLICATION #: M401688
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(CELLAR) UNDERSIZE TAP CONDUCTORS ( TAP OVER 10' )240.21
RSLV 01/11/2018 01/11/2018 09/10/2018
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(CELLAR) METER ENCLOSURE : NEUTRAL BONDED AFTER S. SW.250.24
RSLV 01/11/2018 01/11/2018 09/10/2018
 
003 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(CELLAR) CABLE DISC. SW. : FLEX. CORD AS PERMANENT WIRING400.8
RSLV 01/11/2018 01/11/2018 09/10/2018
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(CELLAR) EMT NOT SECURED 358.30
RSLV 01/11/2018 01/11/2018 09/10/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order