BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M401642
Premises: 1481 5 AVENUE MANHATTAN BIN: 1087768     Block: 1746   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1485 5 AV Census Tract:   198 Health Area:  1600
APT # 18B Admin Area:   M - MANHATTAN Inspection Area:   H
NEW YORK, NY 10035 Community Board:   111
DOB Cross Street(s):   EAST 119 STREET,    EAST 120 STREET
Status:   C - JOB IS SIGNED OFF 09/16/2019 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/18/2017 9:34 PM
Application Entered:   09/18/2017 Job Start Date:   09/18/2017
Last Change:   09/16/2019 Job End Date:   03/17/2018
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     07/30/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011485 Licensee Name: BENJAMIN DREBIN
Firm: 002950 Firm Name: ACCURATE ELEC'L CORP.
Firm Phone: 718-606-9181  Firm Address: 11-07 43RD ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $56.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTHONY MULJADI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
018  18B  10  36    20  10             
Buildings Total 10  36    20  10                
Total Units : 76 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/06/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  B1A2R3R4Y5-C- APT 18B EXISTING CIRCUITS ( EXTENSION OF CIRCUITRY ONLY )

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401642
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2019 06/06/2019 DNM V (46) (1)
INSPECTION COMMENTS: ELECTRICIAN MUST FILE PAA FOR PANEL, AND ALL DEVICES THROUGHOUT.(APT 18B). ONLY THE KITCHEN WAS CERTIFIED AND CLOSED ON APPLICATION M401279.
 
(2) 07/30/2019 07/30/2019 TUR C R (1) (0)
INSPECTION COMMENTS: SEE REQ COMMENTS

OBJECTION FOR APPLICATION #: M401642
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 018)(APT 18B).ELECTRICIAN MUST FILE PAA FOR PANEL, AND ALL DEVICESTHROUGHOUT.
RSLV 06/06/2019 06/06/2019 07/30/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back