| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
1, 200AMP |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 SET OF 4/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
200AMP |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (GROUND FLOOR) SERVICE SWITCH 110.12 |
RSLV |
02/22/2018 |
02/22/2018 |
06/02/2018 |
| |
| 002 |
(999) |
OTHER (GROUND FLOOR) SERVICE SWITCH NOT READILY ACCESSIBLE 230.70 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 003 |
(999) |
OTHER (GROUND FLOOR) PANEL IN VICINITY OF CLOTHING 240.24 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 004 |
(999) |
OTHER (GROUND FLOOR) SERVICE SW. HAS NO GROUND TO WATER MAIN 250.53 |
RSLV |
02/22/2018 |
02/22/2018 |
06/02/2018 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR) GROUND ROD TERMINATION IN WALL 250.68 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR) SERVICE ENTRANCE RACEWAY NO BOND 250.102 |
RSLV |
02/22/2018 |
02/22/2018 |
06/02/2018 |
| |
| 007 |
(999) |
OTHER (GROUND FLOOR) SERVICE ENTRANCE CONDUIT NEEDS SUPPORT 344.30 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 008 |
(999) |
OTHER (GROUND FLOOR) ARC FLASH STICKERS WHERE REQUIRED 110.16 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 009 |
(999) |
OTHER (GROUND FLOOR) LIGHTS WITH WHITE SJ CORD NO BUSHING TOUT 400.14 |
RSLV |
02/22/2018 |
02/22/2018 |
04/18/2018 |
| |
| 010 |
(999) |
OTHER (GROUND FLOOR) END LINE BOX COVER PLYWOOD 110.3 110.11 |
RSLV |
02/22/2018 |
02/22/2018 |
06/02/2018 |
| |
| 011 |
(999) |
OTHER (GROUND FLOOR) SERVICE NOT IN FIRE RATED ROOM 230.6 |
RSLV |
04/18/2018 |
04/18/2018 |
06/02/2018 |
| |
| 012 |
(999) |
OTHER (GROUND FLOOR) COLLECTIVE BAR NOT PROPER SIZE 250.64 |
RSLV |
04/18/2018 |
04/18/2018 |
06/02/2018 |