Electrical Application Details for App #: M401489
Premises: 52 LUDLOW STREET MANHATTAN BIN: 1004025     Block: 310   Lot: 9
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 52 LUDLOW ST Census Tract:   16 Health Area:  7400
ENTIRE Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   HESTER STREET,    GRAND STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/14/2017 7:55 AM
Application Entered:   09/14/2017 Job Start Date:   09/14/2017
Last Change:   08/22/2025 Job End Date:   08/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     06/03/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011440 Licensee Name: MARIO F CASTRO
Firm: 004009 Firm Name: POWER SURGE ELECTRIC, INC
Firm Phone: 718-276-9797  Firm Address: 122-20 MONTAUK STREET SPRINGFIELD GARDENS NY 11413 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $547.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LILY L FUNG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001    20  18  10             
002    20  18  10             
003    20  18  10             
004    20  18  10             
005    20  18  10             
Buildings Total 105  95  10  34  54                
Total Units : 298 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 1 #10-Wire 0
Existing Meters 11 + New Meters 11 - Removed Meters 11 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/14/2017 Notice: 1 - FIRST NOTICE 06/04/2019
Power Issued: 09/14/2017 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401489
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/17/2019 04/17/2019 PHG V (75) (19)
INSPECTION COMMENTS: ALL SERVICE TEMP OUT RE INSPECT OF SERVICE NEEDED AND ALL AC DISCONNECTS T OUT DUE TO WORK SPACE. CONTRACTOR TO FILE FOE ALL WORK INCLUDING FEEDERS MOTORS HEATERS DEVICE COUNT NO A/C OUTLETS INSTALLED
 
(2) 06/03/2019 06/04/2019 SWR V R (120) (2)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. OBJECTION ISSUED.

OBJECTION FOR APPLICATION #: M401489
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 004) GFCI PROTECTION MISSING 4 FLOOR KITCHEN COUNTER 210.8
RSLV 04/17/2019 04/17/2019 06/03/2019
 
002 (229) SPLICE BOXES NOT ACCESSIBLE
(FLOOR: 006) NO ACCESS TO HOOD WIRES IN TOP FLOOR APT 314.29
RSLV 04/17/2019 04/17/2019 06/03/2019
 
003 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(ALL FLOORS)NO WORKING SPACE FOR ALL PANELS A LINE(INSIDE CLOTHES CLOSETS)110.26
RSLV 04/17/2019 04/17/2019 06/03/2019
 
004 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) 2 WIRES UNDER 1 LUG FOR STOVE OUTLET ALL APTS 110.3
RSLV 04/17/2019 04/17/2019 06/03/2019
 
005 (283) SMALL APPLIANCE OUTLETS NOT PROPERLY LOCATED
(ALL FLOORS)ALL B LINE MISSING KITCHEN COUNTER OUTLET ON 12 INCH SPACE 210.52
RSLV 04/17/2019 04/17/2019 06/03/2019
 
006 (340) RECEPTACLES NOT TAMPERPROOF
(ALL FLOORS)TAMPER OUTLETS MISSING 3 FLOOR UP KITCHEN BATHROOM ECT 406.11
RSLV 04/17/2019 04/17/2019 06/03/2019
 
007 (356) RACEWAY LACKS MECHANICAL CONTINUITY
(ALL FLOORS)BROKEN CONCENTRIC KO IN ALL B LINE PANELS FOR FEEDER 250.96 300.10
RSLV 04/17/2019 04/17/2019 06/03/2019
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS)NO GFCI FOR CEILING EXHAUST FANS IN ALL BATHE ROOM AS PERMANUFACTURE (PAPER WORK NEEDED) 110.3 210.8
RSLV 04/17/2019 04/17/2019 06/03/2019
 
009 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)NO AFCI FOR 120V CKTS PROVIDED IN ALL NEEDED AREAS 210.12
RSLV 04/17/2019 04/17/2019 06/03/2019
 
010 (999) OTHER
(ALL FLOORS) APP DOES NOT MATCH INSTALL T OUT
RSLV 04/17/2019 04/17/2019 06/03/2019
 
011 (999) OTHER
(ALL FLOORS)ALL PANELS IN ALL A LINE APTS LOCATED IN CLOTHES CLOSET 240.24
RSLV 04/17/2019 04/17/2019 06/03/2019
 
012 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(BASEMENT) SERVICE RM TEMPED OUT 590.3
RSLV 04/17/2019 04/17/2019 06/03/2019
 
013 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(BASEMENT) UN TERMINATED CABLE IN BSMT CEILING SERVICE RM 330
RSLV 04/17/2019 04/17/2019 06/03/2019
 
014 (261) ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES
(BASEMENT) ELE ROOM USED AS STORAGE
RSLV 04/17/2019 04/17/2019 06/03/2019
 
015 ( 30) OUTLET BOXES ARE NOT SECURED
(BASEMENT) NO SUPPORT FRO FLOOR BOX IN KITCHEN 314.1
RSLV 04/17/2019 04/17/2019 06/03/2019
 
016 ( 30) OUTLET BOXES ARE NOT SECURED
(BASEMENT) NO BOX SUPPORT FOR BOX IN CEILING SERVICE RM
RSLV 04/17/2019 04/17/2019 06/03/2019
 
017 (999) OTHER
(BASEMENT)LOAD CALCULATION NEEDED FOR 400 AMP SERVICE WITH 10 APTS WITH 9 50AMP STOVES 10 30 AMP A/C 10 WASHER /DRYER PLUS ALL OTHER LOADS220.40
RSLV 04/17/2019 04/17/2019 06/03/2019
 
018 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(GROUND FLOOR)NO WORK SPACE FOR ALL AC DISCONNECTS GRND FLOOR BACK 110.26
RSLV 04/17/2019 04/17/2019 06/03/2019
 
019 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(ROOF) NO WORKING SPACE FOR ALL AC DISCONNECTS ON ROOF 110.26
RSLV 04/17/2019 04/17/2019 06/03/2019
 
020 (999) OTHER
(ALL FLOORS)NO WORKING SPACE FOR ALL A/C DISCONNECTS ON ROOF / GROUND FLOOR. ART110.26
OPEN 06/03/2019 06/03/2019
 
021 (999) OTHER
(ALL FLOORS)LOAD CALCULATION NEEDED FOR 400 AMPS SERVICE WITH 10 APTS , 9 50 AMPSTOVES, 10 30 AMPS A/C, 10 WASHER/ DRYER AND ALL OTHER LOADS. ART220.40
OPEN 06/03/2019 06/03/2019