| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 004) APT 4C MADISON CABINET OUTLET NO TR TYPE ART .406.11 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 002 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 004)APT 4C MADISON CABINET OUTLET NOT GFCI PROTECTED ART 210.8 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 003 |
(146) |
APPLIANCE DISCONNECT NOT PROPERLY LOCATED/LOCKABLE (ALL FLOORS)DISHWASHER DISCONNECT NOT PROPERLY LOCATED/ LOCKABLE ART 422.31422.30 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 004 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ARC FLASH LABEL NOT PROVIDED T-OUT ART. 110.16 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 005 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (BASEMENT)FIRE PUMP SUPPLY CONDUCTORS NOT INSTALLED OUTSIDE OR CONCRETE INCASE(PIPE NOT RIGID) AM. 695.6, AM 230.6, ART 230 6, ART 695.6 E |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 006 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (BASEMENT) BUSTER PUMP WIRE OVER FUSED ART 310.16 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) 600 AMP DISCONNECT FUSED NOT AS PER A/B DRAWINGS AM110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)WIRES FROM ATS TO THE FA NOT AS PER AB DRAWINGS (VITALINK CABLE AM110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)100 AMP FIRE ALARM SWITCH FUSED NOT AS PER AB DRAWINGS AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)2500 AMP FIRE PUMP DISCONNECT NOT FUSED AS PER AB DRAWINGS AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)400 AMP SS NOT AS AB DRAWINGS (NOT IN USE SPARE) AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)SETS OF WIRES FROM MAIN DISTRIBUTION CABINET AND TROUGH (5 SETS OF400 MCM) AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)600 AMP DISCONNECT FUSE SIZE AND FUSE TYPE NOT AS PER AB DRAWINGSAM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)200 AMP SWITCH NOT IN USE SPARE NOT AS PER AB DRAWINGS AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 015 |
( 29) |
OUTLET BOXES ARE NOT COVERED (BASEMENT) METAL BOX MISSING COVERS T-OUT ART 314.25 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 016 |
( 45) |
FIXTURE NOT INSTALLED IN AN APPROVED MANNER (BASEMENT) DROP CEILING LIGHTS NOT SUPPORTED T-OUT ART 410.30 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 017 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ROOF)400 AMP DISCONNECT FOR WATER COOLER ( CHILLER ) MODIFICATION AM110.2 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 018 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ROOF) GENERATOR GROUND NOT AS PER AB DRAWINGS AM 110.2B |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 019 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ROOF) CHILLER DISCONNECT MISSING BUSHING ART. 300.11 |
RSLV |
08/16/2020 |
08/16/2020 |
12/06/2020 |
| |
| 020 |
(145) |
APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED. (ALL FLOORS)APPLIANCE DISCONNECT NOT PROVIDED IDENTIFIED 422.30, AT KITCHENAREA, ALL FLR. |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 021 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ARC FLASH LABEL NOT PROVIDED T-OUT ART. 110.16, GENERATOR RM DISSW, AND CELLAR. |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 022 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ALL APT, 314.29, |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 023 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)250.122, 30 AMP DRYER RECEPTACLE GROUNDING CONDUCTOR UNDERSIZE, ALLAPT. |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 024 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (ALL FLOORS)ALL FLR,314.29, JUNCTION NOT ACCESSIBLE, AT KITCHEN, BEHINDAPPLIANCE. |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 025 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) 210.8 (7) LAUNDRY RECEPTACLE WITHIN 1.8 M (6 FT) OF THE OUTSIDEEDGE OF THE SINK/NOT GFCI PROTECTED , ALL APPT. |
RSLV |
12/06/2020 |
12/06/2020 |
04/09/2021 |
| |
| 026 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (CELLAR) 590.3(D), TEMP WIRING IN USED, ABOVE DROP CEILING. |
RSLV |
12/06/2020 |
12/06/2020 |
04/09/2021 |
| |
| 027 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) 250.50,52 ALL GROUNDING ELECTRODE PRESENT AT EACH BUILDING ORSTRUCTURE SERVED SHALL BE BONDED, TWO SERVER BUILDING, NOT BONDED. |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 028 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AT SER SW SECT 2, 400 AMP BUCKET, FUSE AT 400 AMP, REQUIRED 300 AMPAS PER DRAWING. |
RSLV |
12/06/2020 |
12/06/2020 |
04/09/2021 |
| |
| 029 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AT SECT 2 SER SW, 600 AMP BUCKET, FUSE AT 500 AMP, AS PER DRAWINGREQUIRED 600 AMP. |
RSLV |
12/06/2020 |
12/06/2020 |
04/09/2021 |
| |
| 030 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ROOF) GENERATOR FRAME NOT BONDED 250.34(C). |
RSLV |
12/06/2020 |
12/06/2020 |
05/04/2021 |
| |
| 031 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AM. 110.2 FUSE TYPE AND OPENING OF EXIT DOORS NOT PERDRAWING |
RSLV |
04/09/2021 |
04/09/2021 |
05/04/2021 |