BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M401323
Premises: 26 EAST 11 STREET MANHATTAN BIN: 1009259     Block: 568   Lot: 16
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26 E 11TH ST Census Tract:   61 Health Area:  5700
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 04/28/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/11/2017 1:15 PM
Application Entered:   09/11/2017 Job Start Date:   09/11/2017
Last Change:   04/28/2018 Job End Date:   09/11/2018
Appointment Status:   
Last Inspection By:   RILEY (MONTY) MONTAGUE       On     04/25/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011350 Licensee Name: VINCENT BUONO
Firm: 002760 Firm Name: LAREDO ELECTRIC, INC.
Firm Phone: 718-227-6607  Firm Address: 2477 ARTHUR KILL ROAD STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $145.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RESIDENTAL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROSEMARY PAPARO
Owner Business Name: BUCHBINDER & WARREN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  200 AMP SERVICE SW. REPLA
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  1 SET 3/0
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/05/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE DAMAGE END LINE BOX

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401323
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/23/2017 10/24/2017 STP V (45) (3)
INSPECTION COMMENTS: FAIL. SERVICE SWITCH ADDED IN FIELD.
 
(2) 12/05/2017 12/05/2017 MQY V Y (65) (1)
INSPECTION COMMENTS: PARTIALLY REMOVED
 
(3) 04/25/2018 04/25/2018 MYT C R (20) (0)
INSPECTION COMMENTS: JOB CERTIFIED

OBJECTION FOR APPLICATION #: M401323
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) SERVICE ENTRANCE CONDUIT CONTINUITY 300.10
RSLV 10/23/2017 10/23/2017 12/05/2017
 
002 (999) OTHER
(BASEMENT) 2/0 OVERFUSED AT SERVICE SWITCH 240.4
RSLV 10/23/2017 10/23/2017 12/05/2017
 
003 (999) OTHER
(BASEMENT) WATER CAN ENTER END LINE BOX 110.11
RSLV 10/23/2017 10/23/2017 04/25/2018
 
004 (999) OTHER
(BASEMENT)NEMA 1 RATED ENDLINE BOX NOT RATED FOR DRIPPING OR SPLASHING OFWATER (ENDLINE BOX LOCATED BELOW GROUND LEVEL UNDERNEATH A STREETFLOOR GRATE (110.2)*LOOK AT NEMA RATINGS
RSLV 12/05/2017 12/05/2017 04/25/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order