| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1-100A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
2 |
1-3#3 AWG; 1-4#6 AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
1 3/0, #4 GROUND |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
1-225A; 1-125A |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (SUB-CELLAR) LIGHTS NEED SUPPORTS 410.36 |
RSLV |
01/25/2018 |
01/25/2018 |
06/13/2019 |
| |
| 002 |
(999) |
OTHER (SUB-CELLAR) TEMPS NOT REMOVED FROM CEILING 590.3 |
RSLV |
01/25/2018 |
01/25/2018 |
05/24/2018 |
| |
| 003 |
(999) |
OTHER (SUB-CELLAR) RECEPTACLE MC BOX NEEDS BOND 250.148 |
RSLV |
01/25/2018 |
01/25/2018 |
05/24/2018 |
| |
| 004 |
(999) |
OTHER (SUB-CELLAR) TRANSFORMER SECONDARY TAPPED 240.21 |
RSLV |
01/25/2018 |
01/25/2018 |
05/23/2019 |
| |
| 005 |
(999) |
OTHER (SUB-CELLAR) PANTRY UNDER COUNTER LIGHT CONNECTOR BROKE 330.40 |
RSLV |
01/25/2018 |
01/25/2018 |
05/24/2018 |
| |
| 006 |
(999) |
OTHER (SUB-CELLAR) DIRECTORY FOR SMALL PANEL 408.4 |
RSLV |
01/25/2018 |
01/25/2018 |
05/24/2018 |
| |
| 007 |
(999) |
OTHER (SUB-CELLAR) FLEX CORD IN CEILING ABOVE TRANSFORMER 400.8 |
RSLV |
01/25/2018 |
01/25/2018 |
05/24/2018 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (CELLAR)PANTRY: WATER FOUNTAIN NOT GFCI PROTECTED 422.52 |
RSLV |
05/24/2018 |
05/24/2018 |
05/23/2019 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)1 FLOOR, 314.4, METAL BOXES MUST BE GROUNDED, JUNCTION BOXESPROVIDED FOR LIGHT FIXTURE ARE NOT GROUNDED THRU-OUT. |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 010 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (CELLAR)314.29, TROUGH / SPLICE BOXES, INSTALL BETWEEN WALL ABOVE DROPCEILING, WITH HIGH VOLTAGE CONDUCTOR ARE NOT ACCESSIBLE,/ BURIED. |
RSLV |
05/23/2019 |
05/23/2019 |
07/16/2019 |
| |
| 011 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED (CELLAR)110.14, TRANSITION BOXES,/ JUNCTION BOXES ABOVE CEILING MULTIPLEGROUND CONDUCTOR PROVIDED AT JUNCTION BOX ARE NOT PROPERLYTERMINATE. |
RSLV |
05/23/2019 |
05/23/2019 |
07/16/2019 |
| |
| 012 |
(999) |
OTHER (CELLAR) 348.60, FMC ARE NOT FULLY BOND AT TRANSFORMER. |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 013 |
(999) |
OTHER (CELLAR)CONTRACTOR TO PROVIDED, DISCONNECT SWITCH, FEEDER FOR TRANSFORMERLOCATED IN CELLAR, INSTALL. |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 014 |
(999) |
OTHER (CELLAR) 110.21/22, DIS SW ARE NOT LABEL AT STORAGE RM. |
RSLV |
05/23/2019 |
05/23/2019 |
07/16/2019 |
| |
| 015 |
(999) |
OTHER (CELLAR)250.110, A/C DIS SW, EQUIPMENT GROUNDING AND EQUIPMENT GROUNDINGCONDUCTOR FIX IN PLACE. |
RSLV |
05/23/2019 |
05/23/2019 |
07/16/2019 |
| |
| 016 |
( 11) |
FEEDER CONDUCTORS ARE NOT OF PROPER SIZE (GROUND FLOOR)400.8, FLEX CORD IN USED ABOVE DROP CEILING, THRU-OUT. |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 017 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (GROUND FLOOR) 590.3(D), ABOVE DROP CEILING TEMP WIRE IN USED. |
RSLV |
05/23/2019 |
05/23/2019 |
07/16/2019 |
| |
| 018 |
( 29) |
OUTLET BOXES ARE NOT COVERED (GROUND FLOOR) 314.25, OPEN JUNCTION ABOVE DROP CEILING, |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 019 |
( 30) |
OUTLET BOXES ARE NOT SECURED (GROUND FLOOR)314.23, JUNCTION BOXES NOT SECURED ABOVE DROP CEILING. |
RSLV |
05/23/2019 |
05/23/2019 |
06/13/2019 |
| |
| 020 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (CELLAR)CELLAR 320.30 ARMORED CABLE ARE NOT PROPERLY SECURED ( T-OUT DROPCEILING) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 021 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (CELLAR)CELLAR 110.12(A) KO'S ARE NOT CLOSED , OUTLET BOXES , DROP CEILING (ELECTRICAL PANEL AREA) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 022 |
(999) |
OTHER (CELLAR)CELLAR CONTRACTOR TO FILE PAA ( OBSERVED : 1- HEATER/ 1 SET 4# 3/0AWG) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 023 |
(999) |
OTHER (CELLAR)CELLAR 348.30 FMC ARE NOT SECURING AND SUPPORTING ( DROP CEILING .FEEDER FROM SECONDARY XFMR) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 024 |
(999) |
OTHER (CELLAR)CELLAR 110.22 MISSING LABEL AT FA DISCONNECT SW ( 30 A DISCONNECT SW) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 025 |
(999) |
OTHER (CELLAR)CELLAR 400.14 NOT PROVIDE LISTED FITTING FOR FLEX CORD ( SUB- METER) ( ELECTRICAL PANELS AREA) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 026 |
(999) |
OTHER (CELLAR)CELLAR 250.8(A) ON EGC BAR NOT PROVIDED MACHINE SCREWS ( PULL BOXON DROP CEILING) ( TOP OF ELECTRICAL PANELS) |
RSLV |
06/13/2019 |
06/13/2019 |
07/16/2019 |
| |
| 027 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (SUB-CELLAR)SUB 320.30 ARMORED CABLE ARE NOT PROPERLY SECURED ( ELECTRICALPANEL AREA, DROP CEILING) |
RSLV |
07/16/2019 |
07/16/2019 |
08/30/2019 |
| |
| 028 |
(999) |
OTHER (SUB-CELLAR) SUB CONTRACTOR TO FILE PAA ( 1- HEATER) |
RSLV |
07/16/2019 |
07/16/2019 |
09/16/2019 |
| |
| 029 |
(999) |
OTHER (SUB-CELLAR) SUB AM 760.41 NOT PROVIDED LABEL ON FA DISCONNECT SW |
RSLV |
07/16/2019 |
07/16/2019 |
08/22/2019 |