Electrical Application Details for App #: M401133
Premises: 641 5 AVENUE MANHATTAN BIN: 1035481     Block: 1287   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 645 FIFTH AV Census Tract:   102 Health Area:  4800
SC1 LEVEL Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   FURLA STOCK ROOM
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 09/16/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/06/2017 10:11 AM
Application Entered:   09/06/2017 Job Start Date:   09/06/2017
Last Change:   09/16/2019 Job End Date:   10/27/2017
Appointment Status:   
Last Inspection By:   RIVERA, F       On     09/16/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012242 Licensee Name: PATRICK MIELE
Firm: 003983 Firm Name: LITESPEED ELECTRIC, INC
Firm Phone: 212-947-3200  Firm Address: 135 WEST 29TH STREET, STE 301 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $256.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: OXFORD PROPERTIES GROUP
Authorized Representative:  MICHAEL CAMPANA
Relationship To Owner:   DIRECTOR CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  1-100A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  1-3#3 AWG; 1-4#6 AWG
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 3/0, #4 GROUND
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  1-225A; 1-125A
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SC1    24  14    24             
SUB  SC1                    75 
Buildings Total 24  14    24               75 
Total Units : 143 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/16/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M401133
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/25/2018 01/26/2018 STP V (50) (7)
INSPECTION COMMENTS: FAIL. TRANSFORMER ADDED IN FIELD. DID NOT SEE PRIMARY OF TRANSFORMER OR SYSTEM BONDING JUMPER. NO ACCESS TO FIRE ALARM DISCONNECT.
 
(2) 03/21/2018 03/21/2018 CLC N (45) (0) Y
INSPECTION COMMENTS: NO ACCESS CONTR. NO SHOW
 
(3) 05/24/2018 05/24/2018 EDB V Y (60) (1)
INSPECTION COMMENTS: INSPECT OBJECTION ONLY. SEE ATTACHMENT.
 
(4) 05/23/2019 05/24/2019 DWB V Y (65) (11)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(5) 06/13/2019 06/13/2019 CDX V Y (60) (7)
INSPECTION COMMENTS: FAIL.
 
(6) 07/10/2019 07/11/2019 TOR N (30) (0) Y
INSPECTION COMMENTS: FAIL
 
(7) 07/16/2019 07/16/2019 CDX V R (60) (3)
INSPECTION COMMENTS: FAIL.
 
(8) 08/22/2019 08/22/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000018615
 
(9) 08/30/2019 08/30/2019 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000019195
 
(10) 09/16/2019 09/16/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000020569

OBJECTION FOR APPLICATION #: M401133
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(SUB-CELLAR) LIGHTS NEED SUPPORTS 410.36
RSLV 01/25/2018 01/25/2018 06/13/2019
 
002 (999) OTHER
(SUB-CELLAR) TEMPS NOT REMOVED FROM CEILING 590.3
RSLV 01/25/2018 01/25/2018 05/24/2018
 
003 (999) OTHER
(SUB-CELLAR) RECEPTACLE MC BOX NEEDS BOND 250.148
RSLV 01/25/2018 01/25/2018 05/24/2018
 
004 (999) OTHER
(SUB-CELLAR) TRANSFORMER SECONDARY TAPPED 240.21
RSLV 01/25/2018 01/25/2018 05/23/2019
 
005 (999) OTHER
(SUB-CELLAR) PANTRY UNDER COUNTER LIGHT CONNECTOR BROKE 330.40
RSLV 01/25/2018 01/25/2018 05/24/2018
 
006 (999) OTHER
(SUB-CELLAR) DIRECTORY FOR SMALL PANEL 408.4
RSLV 01/25/2018 01/25/2018 05/24/2018
 
007 (999) OTHER
(SUB-CELLAR) FLEX CORD IN CEILING ABOVE TRANSFORMER 400.8
RSLV 01/25/2018 01/25/2018 05/24/2018
 
008 ( 53) GFCI HAS NOT BEEN PROVIDED
(CELLAR)PANTRY: WATER FOUNTAIN NOT GFCI PROTECTED 422.52
RSLV 05/24/2018 05/24/2018 05/23/2019
 
009 (999) OTHER
(ALL FLOORS)1 FLOOR, 314.4, METAL BOXES MUST BE GROUNDED, JUNCTION BOXESPROVIDED FOR LIGHT FIXTURE ARE NOT GROUNDED THRU-OUT.
RSLV 05/23/2019 05/23/2019 06/13/2019
 
010 (229) SPLICE BOXES NOT ACCESSIBLE
(CELLAR)314.29, TROUGH / SPLICE BOXES, INSTALL BETWEEN WALL ABOVE DROPCEILING, WITH HIGH VOLTAGE CONDUCTOR ARE NOT ACCESSIBLE,/ BURIED.
RSLV 05/23/2019 05/23/2019 07/16/2019
 
011 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(CELLAR)110.14, TRANSITION BOXES,/ JUNCTION BOXES ABOVE CEILING MULTIPLEGROUND CONDUCTOR PROVIDED AT JUNCTION BOX ARE NOT PROPERLYTERMINATE.
RSLV 05/23/2019 05/23/2019 07/16/2019
 
012 (999) OTHER
(CELLAR) 348.60, FMC ARE NOT FULLY BOND AT TRANSFORMER.
RSLV 05/23/2019 05/23/2019 06/13/2019
 
013 (999) OTHER
(CELLAR)CONTRACTOR TO PROVIDED, DISCONNECT SWITCH, FEEDER FOR TRANSFORMERLOCATED IN CELLAR, INSTALL.
RSLV 05/23/2019 05/23/2019 06/13/2019
 
014 (999) OTHER
(CELLAR) 110.21/22, DIS SW ARE NOT LABEL AT STORAGE RM.
RSLV 05/23/2019 05/23/2019 07/16/2019
 
015 (999) OTHER
(CELLAR)250.110, A/C DIS SW, EQUIPMENT GROUNDING AND EQUIPMENT GROUNDINGCONDUCTOR FIX IN PLACE.
RSLV 05/23/2019 05/23/2019 07/16/2019
 
016 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
(GROUND FLOOR)400.8, FLEX CORD IN USED ABOVE DROP CEILING, THRU-OUT.
RSLV 05/23/2019 05/23/2019 06/13/2019
 
017 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(GROUND FLOOR) 590.3(D), ABOVE DROP CEILING TEMP WIRE IN USED.
RSLV 05/23/2019 05/23/2019 07/16/2019
 
018 ( 29) OUTLET BOXES ARE NOT COVERED
(GROUND FLOOR) 314.25, OPEN JUNCTION ABOVE DROP CEILING,
RSLV 05/23/2019 05/23/2019 06/13/2019
 
019 ( 30) OUTLET BOXES ARE NOT SECURED
(GROUND FLOOR)314.23, JUNCTION BOXES NOT SECURED ABOVE DROP CEILING.
RSLV 05/23/2019 05/23/2019 06/13/2019
 
020 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(CELLAR)CELLAR 320.30 ARMORED CABLE ARE NOT PROPERLY SECURED ( T-OUT DROPCEILING)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
021 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(CELLAR)CELLAR 110.12(A) KO'S ARE NOT CLOSED , OUTLET BOXES , DROP CEILING (ELECTRICAL PANEL AREA)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
022 (999) OTHER
(CELLAR)CELLAR CONTRACTOR TO FILE PAA ( OBSERVED : 1- HEATER/ 1 SET 4# 3/0AWG)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
023 (999) OTHER
(CELLAR)CELLAR 348.30 FMC ARE NOT SECURING AND SUPPORTING ( DROP CEILING .FEEDER FROM SECONDARY XFMR)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
024 (999) OTHER
(CELLAR)CELLAR 110.22 MISSING LABEL AT FA DISCONNECT SW ( 30 A DISCONNECT SW)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
025 (999) OTHER
(CELLAR)CELLAR 400.14 NOT PROVIDE LISTED FITTING FOR FLEX CORD ( SUB- METER) ( ELECTRICAL PANELS AREA)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
026 (999) OTHER
(CELLAR)CELLAR 250.8(A) ON EGC BAR NOT PROVIDED MACHINE SCREWS ( PULL BOXON DROP CEILING) ( TOP OF ELECTRICAL PANELS)
RSLV 06/13/2019 06/13/2019 07/16/2019
 
027 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(SUB-CELLAR)SUB 320.30 ARMORED CABLE ARE NOT PROPERLY SECURED ( ELECTRICALPANEL AREA, DROP CEILING)
RSLV 07/16/2019 07/16/2019 08/30/2019
 
028 (999) OTHER
(SUB-CELLAR) SUB CONTRACTOR TO FILE PAA ( 1- HEATER)
RSLV 07/16/2019 07/16/2019 09/16/2019
 
029 (999) OTHER
(SUB-CELLAR) SUB AM 760.41 NOT PROVIDED LABEL ON FA DISCONNECT SW
RSLV 07/16/2019 07/16/2019 08/22/2019