Electrical Application Details for App #: M400683
Premises: 301 EAST 68 STREET MANHATTAN BIN: 1044753     Block: 1443   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 315 E 68TH ST Census Tract:   118 Health Area:  4400
1Q Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 01/24/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/25/2017 11:44 AM
Application Entered:   08/25/2017 Job Start Date:   08/25/2017
Last Change:   01/24/2018 Job End Date:   08/25/2018
Appointment Status:   
Last Inspection By:   WONG, K.       On     01/19/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012768 Licensee Name: SENAD MEHOVIC
Firm: 004614 Firm Name: E & M ELECTRICAL NY CORP
Firm Phone: 718-281-0158  Firm Address: 193-02 NORTHERN BLVD FLUSHING NY 11358 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $72.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SUSAN SHUPTAR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  1Q    16                 
Buildings Total   16                    
Total Units : 19 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/27/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M400683
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/19/2017 10/19/2017 PHG J (20) (0) Y
INSPECTION COMMENTS: INSPECTED FEEDER ONLY NO ACCESS TO APT
 
(2) 12/27/2017 12/27/2017 AYC V (60) (4)
INSPECTION COMMENTS: FAIL
 
(3) 01/19/2018 01/19/2018 KIW J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000000873
 
(4) 01/19/2018 01/19/2018 KIW J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000000874
 
(5) 01/19/2018 01/19/2018 KIW J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000000875
 
(6) 01/19/2018 01/19/2018 KIW C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000000877

OBJECTION FOR APPLICATION #: M400683
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(FLOOR: 001)MULIT-STAGE KNOCKOUT IS SEPARATING AND THE PANEL IS NOT PROPERLYGROUNDED ART. 320.108, 250.4(A)(5)
RSLV 12/27/2017 12/27/2017 01/19/2018
 
002 (296) PANEL IS LOCATED IN CLOTHES/LINEN CLOSET
(FLOOR: 001)CIRCUIT BREAKER PANEL LOCATED IN HALLWAY CLOSET ART. 110.26
RSLV 12/27/2017 12/27/2017 01/19/2018
 
003 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
(BASEMENT) EMT CONDUIT FOR APARTMENT RISER NOT SUPPORTED ART 358.30
RSLV 12/27/2017 12/27/2017 01/19/2018
 
004 (999) OTHER
(BASEMENT) FIRE STOP NOT INSTALLED AT WALL PENETRATIONS ART 300.21
RSLV 12/27/2017 12/27/2017 01/19/2018