BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M400586
Premises: 1041 PARK AVENUE MANHATTAN BIN: 1047951     Block: 1515   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1045 PARK AV Census Tract:   148.02 Health Area:  3600
APT 2A & 2B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 86 STREET,    EAST 87 STREET
Status:   C - JOB IS SIGNED OFF 11/30/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/23/2017 1:12 PM
Application Entered:   08/23/2017 Job Start Date:   08/23/2017
Last Change:   11/30/2018 Job End Date:   06/25/2018
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     11/08/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012008 Licensee Name: JAROSLAW K KURACH
Firm: 003679 Firm Name: BELMONT ELECTRICAL, INC
Firm Phone: 646-484-6641  Firm Address: 42 WEST 38TH STREET, STE 503 NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $180.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE STEINBERG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  1  3-3/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  200 AMP 42CKT
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2AB  87  70    38  87  20         
Buildings Total 87  70    38  87     20           
Total Units : 302 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 1 + New Meters 1 - Removed Meters 1 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/23/2017 Notice: 1 - FIRST NOTICE 10/29/2018
Power Issued: 08/23/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M400586
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/29/2018 10/29/2018 STP V (60) (3)
INSPECTION COMMENTS: FAIL. INSPECTED BASEMENT RISER AND PANEL ONLY. FULL INSPECT ON REMAINDER.
 
(2) 11/08/2018 11/08/2018 MLF C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M400586
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 002) 3/0 FEEDER SPLICE BOX BURIED IN WALL 314.29
RSLV 10/29/2018 10/29/2018 11/08/2018
 
002 (999) OTHER
(FLOOR: 002)MAX CIRCUIT BREAKERS FOR PANEL PROVIDE MODEL LISTED USE 408.54
RSLV 10/29/2018 10/29/2018 11/08/2018
 
003 (999) OTHER
(BASEMENT) TROUGH END COVER NOT SECURE WITH SCREWS 376.100
RSLV 10/29/2018 10/29/2018 11/08/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order