BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M400578
Premises: 356 EAST 72 STREET MANHATTAN BIN: 1044862     Block: 1446   Lot: 23
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 360 E 72ND ST Census Tract:   126 Health Area:  4200
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/23/2017 11:08 AM
Application Entered:   08/23/2017 Job Start Date:   08/23/2017
Last Change:   08/22/2025 Job End Date:   12/01/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   JOFFRE PENA       On     01/31/2018      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012312 Licensee Name: SAMUEL PALACE
Firm: 004091 Firm Name: DYNAMIC ELEC'L CONTRS INC
Firm Phone: 718-498-7476  Firm Address: 1046 WINTHROP STREET BROOKLYN NY 11212 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $60.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT WEINER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    40  10    40             
Buildings Total 40  10    40                
Total Units : 93 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/01/2018
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M400578
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/31/2018 02/01/2018 JRP V (60) (6)
INSPECTION COMMENTS: LIGHT FIXTURES INSTALLED ON CLOTHED WALL IN FRONT OF WATER FOUNTAIN NOT INSPECTED.

OBJECTION FOR APPLICATION #: M400578
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR)LIGHT FIXTURES IN WATER FOUNTAIN NOT GFCI PROTECTED 680.51(A)
OPEN 01/31/2018 01/31/2018
 
002 (999) OTHER
(GROUND FLOOR) BREAKERS NOT LISTED FOR PANEL 110.3(B)
OPEN 01/31/2018 01/31/2018
 
003 (999) OTHER
(GROUND FLOOR) PANEL MISSING COVER 110.3
OPEN 01/31/2018 01/31/2018
 
004 (999) OTHER
(GROUND FLOOR) NO DIRECTORY 408.4
OPEN 01/31/2018 01/31/2018
 
005 (999) OTHER
(GROUND FLOOR) CONDUIT GOING TO WATER FOUNTAIN NOT BONDED 680.53
OPEN 01/31/2018 01/31/2018
 
006 (999) OTHER
(GROUND FLOOR) ELECTRICAL TROUGH OVER FILL 314.16
OPEN 01/31/2018 01/31/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.