BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M400485
Premises: 20 HUDSON YARDS MANHATTAN BIN: 1088961     Block: 702   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 W 33RD Census Tract:   99 Health Area:  5500
LOBBY, 01, 05, 23, 24, 35, 36 Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   30 HUDSON YARDS TOWER A
DOB Cross Street(s):    10 AVENUE,    HUDSON BOULEVARD EAST
Status:   C - JOB IS SIGNED OFF 06/14/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/21/2017 4:26 PM
Application Entered:   08/21/2017 Job Start Date:   08/31/2017
Last Change:   06/14/2019 Job End Date:   03/31/2019
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     04/26/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012155 Licensee Name: JOHN FOLEY
Firm: 000532 Firm Name: FOREST ELECTRIC CORP.
Firm Phone: 212-318-1500  Firm Address: 1375 BROADWAY, 7TH FLOOR NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122988213
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOEL BRENNER
Owner Business Name: TW NY PROPERTIES LLC
Authorized Representative:  JOEL BRENNER
Relationship To Owner:   VP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  59  28- 3#4, 31-4#2
B. Over #2 to 1/0  1  1-4#1/0
C. Over 1/0 to 250 MCM  15  7-3#4/0, 8 - 3#250
D. Over 250 MCM  1  1-3#600,
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  67  59 - 100 , 1-150, 7-225
D. 3 Phase Over 225 AMPS  9  6-250, 2-400, 1-600
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB    30      30             
001    11  101    16  83  11  11      75 
005    34    10  42      120 
023    747  462    162  934  95  215      240 
024    590  391    59  709  64  102      375 
035    724  295    68  854  53  98      30 
036    768  267    140  871  56  110      30 
Buildings Total 2904  1521    461  3523     541          870 
Total Units : 9820 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/05/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB# 170250 M.MORRONE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M400485
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/05/2019 03/05/2019 MJD V (410) (16)
INSPECTION COMMENTS: FAIL, INSPECTION COMPLETED, FLOOR LOB NOT FINISHED, JOB IN PROGRESS, FLOORS 1 AND 5 INSPECTED PASS, FLOORS 23,24,35 AND 36 OBJECTIONS ISSUED, NEED 4 HOURS FOR NEXT INSPECTION.
 
(2) 04/26/2019 04/29/2019 LV1 C R (100) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M400485
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 023) TEMPORARY WIRING IN USE ART. 590.3
RSLV 03/05/2019 03/05/2019 04/26/2019
 
002 (999) OTHER
(FLOOR: 023) OPEN BOXES ART. 314.25
RSLV 03/05/2019 03/05/2019 04/26/2019
 
003 (999) OTHER
(FLOOR: 023) BOXES SET BACK IN COMBUSTIBLE MATERIALS ART. 314.20
RSLV 03/05/2019 03/05/2019 04/26/2019
 
004 (999) OTHER
(FLOOR: 024) BONDING NOT SUFFICIENT ON 250V PANELS ART. 250.97
RSLV 03/05/2019 03/05/2019 04/26/2019
 
005 (999) OTHER
(FLOOR: 024)HANDLE TIES NOT PROVIDED FOR MULTI WIRE CIRCUITS ART. 210.4
RSLV 03/05/2019 03/05/2019 04/26/2019
 
006 (999) OTHER
(FLOOR: 024)RECEPTACLES IN COMMERCIAL KITCHEN NOT GFCI PROTECTED ART. 210.8
RSLV 03/05/2019 03/05/2019 04/26/2019
 
007 (999) OTHER
(FLOOR: 024) TEMPORARY WIRING IN USE ART. 590.3
RSLV 03/05/2019 03/05/2019 04/26/2019
 
008 (999) OTHER
(FLOOR: 024)FIRE STOPPING NOT PROVIDED WHERE FLOOR PENETRATED ART. 300.21
RSLV 03/05/2019 03/05/2019 04/26/2019
 
009 (999) OTHER
(FLOOR: 035) TEMPORARY CONSTRICTION WIRING IN USE ART. 590.3
RSLV 03/05/2019 03/05/2019 04/26/2019
 
010 (999) OTHER
(FLOOR: 035)RECEPTACLE WITHIN 6' OF SINK NOT GFCI PROTECTED ART. 210.8
RSLV 03/05/2019 03/05/2019 04/26/2019
 
011 (999) OTHER
(FLOOR: 035)RECEPTACLES IN COMMERCIAL KITCHEN NOT GFCI PROTECTED ART. 210.8
RSLV 03/05/2019 03/05/2019 04/26/2019
 
012 (999) OTHER
(FLOOR: 035)HANDLE TIES NOT PROVIDED FOR MULTI WIRE CIRCUITS ART. 210.4
RSLV 03/05/2019 03/05/2019 04/26/2019
 
013 (999) OTHER
(FLOOR: 035)HI HATS NOT PROPERLY SUPPORTED ON SUSPENDED CEILING ART. 410.30
RSLV 03/05/2019 03/05/2019 04/26/2019
 
014 (999) OTHER
(FLOOR: 036) BUSHING MISSING IN THE PANEL ART. 300.4
RSLV 03/05/2019 03/05/2019 04/26/2019
 
015 (999) OTHER
(FLOOR: 036) HANDLE TIES MISSING FOR MULTI WIRE CIRCUITS ART. 210.4
RSLV 03/05/2019 03/05/2019 04/26/2019
 
016 (999) OTHER
(FLOOR: 036) HI HATS NOT SECURED ON SUSPENDED CEILING ART. 410.30
RSLV 03/05/2019 03/05/2019 04/26/2019