| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
2 |
2-200A 480V 3 PHASE |
| C. 201 Up to 600 AMPS |
1 |
1-400A 480V 3 PHASE |
| D. 601 Up to 1200 AMPS |
4 |
4-1200A |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
1-(3)1/0AWG |
| C. Over 1/0 to 250 MCM |
1 |
1-(4)4/0AWG |
| D. Over 250 MCM |
172 |
162-(4)600MCM, 4-(3)600 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(124) |
TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE (FLOOR: 015)240.21 SECONDARY TAP OVER 25' FOR F/P DISC. SW. |
RSLV |
01/16/2020 |
01/16/2020 |
07/18/2020 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM. 110.2 EQUIPMENT AND INSTALLATION NOT PER DRAWING |
RSLV |
01/16/2020 |
01/16/2020 |
07/18/2020 |
| |
| 003 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) 250.50,52 BUILDING HAS 3 WATER MAIN |
RSLV |
01/16/2020 |
01/16/2020 |
07/18/2020 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-B1 200 AMP FIRE DISCONNECT TAP NOT ON DRAWINGS 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 005 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 SECTION 4 1600AT GROUND NOT AS PER ADVISORY BOARD(#4) 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 006 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 FIRE ALARM DISCONNECT LOAD SIDE GROUND NOT AS PERADVISORY BOARD (#6) |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 007 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 MCB-A1 MCB-A1 LOCATION NOT AS PER ADVISORY BOARD110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 TCB-1 14 SETS OFF 750 MCM NOT AS PER ADVISORYBOARD 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 009 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 TCB-A1 LOCATION NOT AS PER ADVISORY BOARD 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-A1 FIRE ALARM DISCONNECT TAP OVER 25 ' 240.21 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-B1 MCB-B1 LOCATION NOT AS PER ADVISORY BOARD 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 012 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-B1 SECTION 4 1600 AT GROUND NOT AS PER ADVISORY BOARD110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 013 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-B1 5000 TCB-1 SETS OFF 14 750 MCM NOT AS PER ADVISORYBOARD 110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 015)DESS-PES-SB-15-B1 5000 TCB-B1 NOT AS PER ADVISORY DRAWINGS LOCATION110.2 |
RSLV |
02/21/2020 |
02/21/2020 |
07/18/2020 |