BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M399834
Premises: 306 EAST 5 STREET MANHATTAN BIN: 1006207     Block: 446   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 306 E 5 ST Census Tract:   38 Health Area:  6500
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 04/09/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/08/2017 11:18 AM
Application Entered:   08/08/2017 Job Start Date:   08/09/2017
Last Change:   04/09/2019 Job End Date:   12/22/2017
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     04/09/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011683 Licensee Name: SILVANO TRAVALJA
Firm: 003348 Firm Name: SAMCO ELECTRIC CORP.
Firm Phone: 718-204-2433  Firm Address: 37-35 9TH STREET L.I.C. NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $64.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: OSTAP YURVIV
Owner Business Name: 306-8 SWA LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  2  (1)WATER HEATER(1) BOILER

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
Buildings Total                     
Total Units : 2 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/26/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M399834
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/26/2018 02/26/2018 TOR N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR PRESENT BUT NO ACCESS TO BLDG.
 
(2) 03/25/2019 03/26/2019 DWB V (25) (4)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(3) 04/09/2019 04/09/2019 PHG C R (15) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M399834
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) 314.25, CONDUIT LET ARE NOT INSTALL.
RSLV 03/25/2019 03/25/2019 04/09/2019
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) 110.12(A), KO SEAL NOT INSTALL AT ELECTRICAL PANEL
RSLV 03/25/2019 03/25/2019 04/09/2019
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) 358.30, EMT PIPE NOT SUPPORTED.
RSLV 03/25/2019 03/25/2019 04/09/2019
 
004 (999) OTHER
(BASEMENT) 110.16, ARCH FLASH LABEL NEED AT ELECTRICAL PANEL.
RSLV 03/25/2019 03/25/2019 04/09/2019