BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M399643
Premises: 35 COOPER SQUARE MANHATTAN BIN: 1090311     Block: 461   Lot: 8
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 200 E 6TH ST Census Tract:   38 Health Area:  6500
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):   COOPER SQUARE,    TARAS SHEVCHENKO PLACE
Status:   C - JOB IS SIGNED OFF 10/16/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/03/2017 2:52 PM
Application Entered:   08/03/2017 Job Start Date:   08/03/2017
Last Change:   10/16/2017 Job End Date:   09/30/2017
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     10/16/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012718 Licensee Name: JUAN F JIMENEZ
Firm: 004631 Firm Name: JAVELIN ELECTRIC INC
Firm Phone: 212-683-3500  Firm Address: 36-13 22ND STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $85.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ARUN I BHATIA
Owner Business Name: COOPER & 6TH PROPERTY LLC
Authorized Representative:  PAUL RATNOFSKY
Relationship To Owner:   OWNER'S REPRESENTATIVE


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3/0 #6G
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 0 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/03/2017 Notice: 1 - FIRST NOTICE 09/25/2017
Power Issued: 08/03/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M399643
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/25/2017 09/25/2017 STP V (30) (2)
INSPECTION COMMENTS: FAIL. NEW 200 AMP 2ND LEVEL SWITCH OFF 1200 AMP SERVICE SW #2 CHANGED FROM ITS ORIGINAL INSTALL. ROOM OVER 5000 AMPS. ADVISORY BOARD SUBMISSION REQUIRED.
 
(2) 10/16/2017 10/16/2017 CBK C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M399643
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT) 200A 2ND LEVEL OFF 1200A 1ST LEVEL ALTERED 110.2
RSLV 09/25/2017 09/25/2017 10/16/2017
 
002 (999) OTHER
(BASEMENT) FUSE COORDINATION 2ND LEVEL 200 1ST 1200 AMND 240.12
RSLV 09/25/2017 09/25/2017 10/16/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.