| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
400 A |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
4#1 |
| C. Over 1/0 to 250 MCM |
2 |
4#3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
125 A |
| D. 3 Phase Over 225 AMPS |
1 |
400 A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 001)MC CABLE NOT TERMINATED IN IT ROOM, OPPOSITE ATM MACHINE. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 001) OPEN BOXES IN CEILING T-OUT. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 003 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 001) BREAKERE BLANKS MISSING PANEL. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 004 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 001) NO PANEL DIRECTORIES. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 001) ARC FLASH STICKERS NEEDED ON EQUIPMENTS. 110.16 |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 001) MC CABLES NOT BONDED IN CEILING SPLICE T-OUT. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 007 |
(126) |
BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN (BASEMENT) NO WATER MAIN GROUND ON SERVICE SWITCH. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 008 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (BASEMENT) SERVICE SWITCH NEUTRAL NOT BONDED. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 009 |
(133) |
NO GROUND ROD: BASEMENT OR OUTSIDE (BASEMENT) NO SUPPLEMENTAL GROUND PROVIDED FOE SERVICE. |
RSLV |
01/17/2018 |
01/17/2018 |
03/27/2018 |
| |
| 010 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (BASEMENT) NO LIGHT PROVIDED FOR SERVICE SW 110.26 |
RSLV |
03/21/2018 |
03/21/2018 |
03/27/2018 |
| |
| 011 |
(999) |
OTHER (BASEMENT) NO FIRE STOPPING PROVIDED IN ELE ROOM 300.21 |
RSLV |
03/21/2018 |
03/21/2018 |
03/27/2018 |