Electrical Application Details for App #: M399330
Premises: 641 5 AVENUE MANHATTAN BIN: 1035481     Block: 1287   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 645 FIFTH AV Census Tract:   102 Health Area:  4800
GROUND FLOOR LOBBY Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   OLYMPIC TOWERS
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 01/15/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/27/2017 4:31 PM
Application Entered:   07/27/2017 Job Start Date:   08/07/2017
Last Change:   01/15/2019 Job End Date:   11/09/2018
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     01/15/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012242 Licensee Name: PATRICK MIELE
Firm: 003983 Firm Name: LITESPEED ELECTRIC, INC
Firm Phone: 212-947-3200  Firm Address: 135 WEST 29TH STREET, STE 301 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $193.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHELLE LANDON
Owner Business Name: OLYMPIC TOWERS CO OXFORD
Authorized Representative:  MICHAEL CAMPANA
Relationship To Owner:   DIRECTOR OF CONSTRUCTION


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB    166  20    10  166             
LOB  245  15                   
003                       
Buildings Total 411  36    10  166                
Total Units : 623 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/13/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  LSE JOB #17-6455GC1

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M399330
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/12/2018 12/13/2018 DWB V (60) (6)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(2) 01/15/2019 01/15/2019 MLF C R (36) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M399330
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (220) DOUBLE LUGGING IN SERVICE SWITCH
(FLOOR: 003)MULTIPLE GROUND CONDUCTOR SPLICE AT JUNCTION, FOLLOWED WITH LEDTRANSFORMERS, TERMINAL NOT PROVIDED.
RSLV 12/12/2018 12/12/2018 01/15/2019
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 003) ABOVE PANE JUNCTION ARE NOT COVERED.
RSLV 12/12/2018 12/12/2018 01/15/2019
 
003 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(FLOOR: 003) KO SEAL NOT INSTALL AT ELECTRICAL PANEL.
RSLV 12/12/2018 12/12/2018 01/15/2019
 
004 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(FLOOR: 003) NEUTRAL CONDUCTOR, NOT INDENTIFIED, AS PER CODE.
RSLV 12/12/2018 12/12/2018 01/15/2019
 
005 (999) OTHER
(FLOOR: 003) 426. HEAT TRACE INSTALL ARE NOT GFCI PROTECTED.
RSLV 12/12/2018 12/12/2018 01/15/2019
 
006 (999) OTHER
(FLOOR: 003)110.16, AT ELECTRICAL PANEL, ARCH FLASH LABEL NOT PROVIDED
RSLV 12/12/2018 12/12/2018 01/15/2019