BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M398858
Premises: 68 5 AVENUE MANHATTAN BIN: 1009618     Block: 576   Lot: 41
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 68 5TH AV Census Tract:   63 Health Area:  5700
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):   EAST 12 STREET,    EAST 13 STREET
Status:   C - JOB IS SIGNED OFF 02/28/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/18/2017 2:16 PM
Application Entered:   07/18/2017 Job Start Date:   07/18/2017
Last Change:   02/28/2019 Job End Date:   10/01/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     10/25/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012718 Licensee Name: JUAN F JIMENEZ
Firm: 004631 Firm Name: JAVELIN ELECTRIC INC
Firm Phone: 212-683-3500  Firm Address: 36-13 22ND STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $49.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: THE NEW SCHOOL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    10  12    10         
Buildings Total 10  12    10              
Total Units : 48 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/15/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M398858
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/22/2017 11/24/2017 PHG L (10) (0) Y
INSPECTION COMMENTS: ADDRESS IS 66 5 AVE
 
(2) 12/15/2017 12/15/2017 AYC V (64) (4)
INSPECTION COMMENTS: FAIL
 
(3) 10/25/2018 10/25/2018 MLF C R (23) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M398858
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (143) LUMINAIRES NOT PROPERLY SUPPORTED/SECURED
(BASEMENT)EMERGENCY EXIT SIGN HANGING FROM EMT FEEDER CONDUIT ART. 358.12
RSLV 12/15/2017 12/15/2017 10/25/2018
 
002 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) MISSING KO'S IN TROUGH ART. 110.12(A)
RSLV 12/15/2017 12/15/2017 10/25/2018
 
003 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(BASEMENT) LOCKNUTS NOT TIGHTENED ON FIXTURE ART. 358.42
RSLV 12/15/2017 12/15/2017 10/25/2018
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) EMT NOT SUPPORTED BETWEEN FIXTURES ART. 358.30
RSLV 12/15/2017 12/15/2017 10/25/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back