Electrical Application Details for App #: M398681
Premises: 301 EAST 63 STREET MANHATTAN BIN: 1044384     Block: 1438   Lot: 1
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 301 E 63 ST Census Tract:   110 Health Area:  4900
APT 15 F Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    QUEENSBORO BRIDGE EXIT
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/17/2017 10:17 AM
Application Entered:   07/17/2017 Job Start Date:   07/17/2017
Last Change:   08/22/2025 Job End Date:   07/17/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     12/27/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010190 Licensee Name: ABE HIMELFARB
Firm: 002663 Firm Name: ALEF ELEC'L CONTR'G INC
Firm Phone: 212-764-2200  Firm Address: 247 WEST 38TH STREET NEW YORK NY 10018 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $70.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GREG GASKE
Owner Business Name: GDC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
015  15F  15  28    12  15             
Buildings Total 15  28    12  15                
Total Units : 70 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 12/28/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  WER FILED TO CLOSE OUT ANOTHER CONTRACTORS APP #M346014

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M398681
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/30/2017 12/01/2017 MLF N (15) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR "CANNOT MAKE APPT"
 
(2) 12/27/2017 12/28/2017 AYC V (103) (8)
INSPECTION COMMENTS: FAIL

OBJECTION FOR APPLICATION #: M398681
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (102) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 015)FLEXIBLE CORD INSTALLED THROUGH WALL COUNTERTOP WALL BACKSPLASHART. 400.8
OPEN 12/27/2017 12/27/2017
 
002 (102) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 015)FLEXIBLE CORD INSTALLED AS PERMANENT WIRING METHOD BETWEEN UNDERCABINET FIXTURES ART. 400.8
OPEN 12/27/2017 12/27/2017
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 015)KNOCKOUT PATCHES MISSING IN CIRCUIT BREAKER PANEL ART. 110.12(A)
OPEN 12/27/2017 12/27/2017
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 015)ARC FAULT PROTECTION HAS NOT BEEN PROVIDED THROUGH OUT THE CLOSETS,HALLWAY, LIVING ROOM AND BEDROOM GENERAL USE AND AIR CONDITIONINGBRANCH CIRCUIT WIRING ART. 210.12
OPEN 12/27/2017 12/27/2017
 
005 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(FLOOR: 015)NO RECEPTACLES ALONG WALL (20' LENGTH) ART. 210.52(A)(1)
OPEN 12/27/2017 12/27/2017
 
006 (999) OTHER
(FLOOR: 015)MULTI WIRE BRANCH CIRCUIT MISSING JUMPER AT BREAKER ART. 210.4
OPEN 12/27/2017 12/27/2017
 
007 (999) OTHER
(FLOOR: 015)OUTLET BOXES SET BACK MORE THAN 3/4" FROM SURFACE ART. 312.3
OPEN 12/27/2017 12/27/2017
 
008 (999) OTHER
(FLOOR: 015) DISHWASHER CONNECTION HAS BEEN ALTERED ART. 110.3
OPEN 12/27/2017 12/27/2017