| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(102) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 015)FLEXIBLE CORD INSTALLED THROUGH WALL COUNTERTOP WALL BACKSPLASHART. 400.8 |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 002 |
(102) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 015)FLEXIBLE CORD INSTALLED AS PERMANENT WIRING METHOD BETWEEN UNDERCABINET FIXTURES ART. 400.8 |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 003 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (FLOOR: 015)KNOCKOUT PATCHES MISSING IN CIRCUIT BREAKER PANEL ART. 110.12(A) |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 015)ARC FAULT PROTECTION HAS NOT BEEN PROVIDED THROUGH OUT THE CLOSETS,HALLWAY, LIVING ROOM AND BEDROOM GENERAL USE AND AIR CONDITIONINGBRANCH CIRCUIT WIRING ART. 210.12 |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 005 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 015)NO RECEPTACLES ALONG WALL (20' LENGTH) ART. 210.52(A)(1) |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 006 |
(999) |
OTHER (FLOOR: 015)MULTI WIRE BRANCH CIRCUIT MISSING JUMPER AT BREAKER ART. 210.4 |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 007 |
(999) |
OTHER (FLOOR: 015)OUTLET BOXES SET BACK MORE THAN 3/4" FROM SURFACE ART. 312.3 |
OPEN |
12/27/2017 |
12/27/2017 |
|
| |
| 008 |
(999) |
OTHER (FLOOR: 015) DISHWASHER CONNECTION HAS BEEN ALTERED ART. 110.3 |
OPEN |
12/27/2017 |
12/27/2017 |
|