Electrical Application Details for App #: M398398
Premises: 223 MADISON STREET MANHATTAN BIN: 1003233     Block: 271   Lot: 45
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 223 MADISON ST Census Tract:   6 Health Area:  7800
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RUTGERS STREET,    JEFFERSON STREET
Status:   C - JOB IS SIGNED OFF 06/16/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/11/2017 4:31 PM
Application Entered:   07/11/2017 Job Start Date:   07/12/2017
Last Change:   06/16/2018 Job End Date:   02/12/2018
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     06/12/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009791 Licensee Name: JOSEPH B JORDAN
Firm: 004329 Firm Name: GOTHAM WIRING LICENSED
Firm Phone: 718-295-6430  Firm Address: 649A EAST 183RD STREET ELECTRICAL CONTRACTORS IN BRONX NY 10458 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $325.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NEIL ELLNER
Owner Business Name: WINDWARD REAL ESTATE
Authorized Representative:  JOSEPH JORDAN
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 20 #4-Wire 3 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/11/2017 Notice: 1 - FIRST NOTICE 06/05/2018
Power Issued: 07/11/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BASEMENT SERVICE ONLY, ALL FEEDERS AND UPSTAIRS WORK PRE-EXISTING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M398398
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/03/2018 05/03/2018 DWB J (50) (4)
INSPECTION COMMENTS: OBJECTION ISSUED,
 
(2) 05/22/2018 05/25/2018 MYT V R (60) (2)
INSPECTION COMMENTS: JOB FAILED
 
(3) 06/05/2018 06/05/2018 MLF V Y (75) (1)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(4) 06/12/2018 06/12/2018 DNM C R (25) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M398398
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(BASEMENT) T-O ,JUNCTION BOX'S TO APT RISER, KNOCKOUT ARE NOT CLOSE IN OUTLET BOX, PANEL ENCLOSURE 110.(A)
RSLV 05/03/2018 05/03/2018 05/22/2018
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
(BASEMENT) TO INSTALL BUSHING FOR 200 AMP DISCONNECT 300.11
RSLV 05/03/2018 05/03/2018 05/22/2018
 
003 (999) OTHER
(BASEMENT) STORE DISCONNECT NEUTRAL , TOUCHING HOT LINE
RSLV 05/03/2018 05/03/2018 05/22/2018
 
004 (999) OTHER
(BASEMENT) TEMPS NOT REMOVED 590.3
RSLV 05/03/2018 05/03/2018 05/22/2018
 
005 (999) OTHER
(BASEMENT) LINE AND LOAD WIRED WRONG
RSLV 05/22/2018 05/22/2018 06/05/2018
 
006 (999) OTHER
(BASEMENT) NEED SUPPOERT FOR 4" PIPES
RSLV 05/22/2018 05/22/2018 06/12/2018
 
007 (325) ELECTRICAL CLOSETS SHALL NOT BE USED FOR OTHER PURPOSES
(CELLAR) EL. ROOM USED FOR STORAGE AM. 110.25
RSLV 06/05/2018 06/05/2018 06/12/2018