Electrical Application Details for App #: M398188
Premises: 501 WEST 30 STREET MANHATTAN BIN: 1089323     Block: 702   Lot: 10
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 501 W 30 ST Census Tract:   99
C Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   HUDSON YARDS
Related Job Number:    121324290
DOB Cross Street(s):    10 AVENUE,    HIGH LINE
Status:   C - JOB IS SIGNED OFF 10/17/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/06/2017 Job Start Date:   06/28/2017
Last Change:   10/17/2018 Job End Date:   06/28/2020
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     10/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011004 Licensee Name: JOHN J DILLON
Firm: 000526 Firm Name: FIVE STAR ELECTRIC CORP.
Firm Phone: 718-641-5000  Firm Address: 101-32 101ST STREET OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
Total Fee:  $3,340.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   OFFICE/RETAIL
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52822     Submittal #: 15A0126  
Owner / Occup: NICK LANZILLOTTO
Owner Business Name: RELATED PROPERTIES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  3  2000A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  26  750 MCM ALUM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  3  2000A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 3 - Removed Meters 0 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/06/2017 Notice: 1 - FIRST NOTICE 07/30/2018
Power Issued: 07/06/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB #9827-TEMP SERVICES (REPLACES APPLICATION #M368611)

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M398188
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/30/2018 07/30/2018 CBK V (95) (4)
INSPECTION COMMENTS: SEE OBJECTIONS DETAILS. I ONLY INSPECT DP ON 5TH FLOOR.
 
(2) 10/04/2018 10/04/2018 CBK C R (150) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED.

OBJECTION FOR APPLICATION #: M398188
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 005) FUSE SIZE IN DP, 5TH FLOOR.
RSLV 07/30/2018 07/30/2018 10/04/2018
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 005) DP WAS REMOVED.
RSLV 07/30/2018 07/30/2018 10/04/2018
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 005) # OF SETS OF CONDUCTORS.
RSLV 07/30/2018 07/30/2018 10/04/2018
 
004 (999) OTHER
(FLOOR: 005) SERVICE SWITCHES NOT MARKED. 230.70
RSLV 07/30/2018 07/30/2018 10/04/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.