| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
11 |
9 30A 2 100 A |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
1 |
BUSS TYPE |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
11 |
11 SETS |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
2 |
350 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
5 |
225A |
| D. 3 Phase Over 225 AMPS |
1 |
600A |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 006) ONE LINE DIAGRAM FROM WHERE NEW BUS DUCT 215.5 |
RSLV |
05/31/2018 |
05/31/2018 |
06/11/2018 |
| |
| 002 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 006)COVERS NEEDED FOR CEILING OUT ON 6TH FLR AND COVER NEEDED FOR LB ON8TH FLR |
OPEN |
06/11/2018 |
06/11/2018 |
|
| |
| 003 |
(999) |
OTHER (FLOOR: 006)KO SEALS NEEDED IN LAB ON 6TH AND 14TH FLOOR FOR BOXES IN CEILING.110.12 |
OPEN |
06/11/2018 |
06/11/2018 |
|
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 008)GFCI PROTECTION NOT PROVIDED NEAR SINK ON 8TH AND 14TH FLR |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 008) 277/480 LABELS NOT PROVIDED 408.60(C)NYC |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 014) BUSHING REQUIRED FOR PANEL 110.3 |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 007 |
(313) |
SIGNAGE NOT PROVIDED FOR ELECTRICAL CLOSET (ALL FLOORS) SIGNAGE NEEDED FOR ELECTRIC CLOSETS ON 6TH AND 14TH FLR |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) ARC FLASH LABELS NOT PROVIDED T-OUT. 110.16 |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) LABELS FOR PANELS AND DISCONNECT NOT PROVIDED 110.22 |
RSLV |
06/11/2018 |
06/11/2018 |
07/11/2018 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS) GROUND TAILS MISSING IN J-BOX IN CEILING 250.148 |
OPEN |
06/11/2018 |
06/11/2018 |
|
| |
| 011 |
(999) |
OTHER (ALL FLOORS) DOUBLE LUG T-OUT ON RECEPTACLE GROUNDS 110.4 |
OPEN |
06/11/2018 |
06/11/2018 |
|
| |
| 012 |
(183) |
DISCONNECT IS NOT READILY ACCESSIBLE (FLOOR: 006) NO POLE PROVIDED FOR BUS DUCT SW 404.8 |
OPEN |
07/11/2018 |
07/11/2018 |
|
| |
| 013 |
(999) |
OTHER (ALL FLOORS) APP DOES NOT MATCH INSTALL |
OPEN |
07/11/2018 |
07/11/2018 |
|