BIS Menu  |  Comments  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M397867
Premises: 343 EAST 63 STREET MANHATTAN BIN: 1044390     Block: 1438   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 340 E 64 ST Census Tract:   110 Health Area:  4900
APT 11D Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/27/2017 2:31 PM
Application Entered:   06/27/2017 Job Start Date:   06/28/2017
Last Change:   08/22/2025 Job End Date:   06/28/2018
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     02/21/2019      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011647 Licensee Name: MATINA KARAGIANNIS
Firm: 003820 Firm Name: DEMAND ELECTRIC INC
Firm Phone: 718-439-1600  Firm Address: 3133 31ST STREET ASTORIA NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $90.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHIRLEY LIU
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  40 AMP, 16 CKTS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
011  45  35  26  45             
Buildings Total 45  35  26  45                
Total Units : 153 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 02/21/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  NION- MATINA

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M397867
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/12/2018 04/12/2018 MLF V (29) (1)
INSPECTION COMMENTS: CONTRACTOR CLAIMS TO HAVE ONLY REPLACED FIXTURES ,DEVICES ,AND PANEL
 
(2) 07/06/2018 07/06/2018 PMK N (24) (0) Y
INSPECTION COMMENTS: NO SHOW-CALLED CONTRACTOR THEY CLAIMED THEY WHERE UNAWARE.
 
(3) 07/13/2018 07/13/2018 STP V X (30) (4)
INSPECTION COMMENTS: FAIL.
 
(4) 08/17/2018 08/17/2018 PHG N (10) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(5) 09/11/2018 09/12/2018 PHG N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(6) 11/29/2018 11/29/2018 MLF H X (32) (0) Y
INSPECTION COMMENTS: ALL OBJECTIONS STILL EXIST
 
(7) 01/07/2019 01/08/2019 AYC V R (59) (1)
INSPECTION COMMENTS: FAIL.
 
(8) 02/21/2019 02/21/2019 PHG V R (25) (3)
INSPECTION COMMENTS: CONTRACTOR TO FIX APP TO REFLECT WORK NO FEEDER ON FILE NO AC OUTLETS INSTALLED

OBJECTION FOR APPLICATION #: M397867
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 011)NO GFCI PROTECTION PROVIDED FOR MEDICINE CABINET RECEPT. NEC 210.8
RSLV 04/12/2018 04/12/2018 01/07/2019
 
002 (999) OTHER
(FLOOR: 011) MEDICINE CABINET RECEPTACLE NOT GROUNDED 250.146
RSLV 07/13/2018 07/13/2018 01/07/2019
 
003 (999) OTHER
(FLOOR: 011) MEDICINE CABINET RECEPTACLE NO TR 406.11
RSLV 07/13/2018 07/13/2018 01/07/2019
 
004 (999) OTHER
(FLOOR: 011) HANDLE TIE NEEDED FOR PANEL 210.4
RSLV 07/13/2018 07/13/2018 01/07/2019
 
005 (999) OTHER
(FLOOR: 011) MEDICINE CABINET RECEPTACLE IMPROPER PLACE 210.52
RSLV 07/13/2018 07/13/2018 01/07/2019
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)ART. 406.11 BATHROOM CABINET RECEPTACLES ARE NOT TR RATED.
RSLV 01/07/2019 01/07/2019 02/21/2019
 
007 (999) OTHER
(FLOOR: 011) APP DOES NOT MATCH INSTALL
OPEN 02/21/2019 02/21/2019
 
008 (999) OTHER
(FLOOR: 011) 2 WIRES UNDER 1 LUG POLARIS FOR NEUTRAL 110.3
OPEN 02/21/2019 02/21/2019
 
009 (999) OTHER
(FLOOR: 011) NO COVER FOR EXISTING PULL BOX 314
OPEN 02/21/2019 02/21/2019