BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M397754
Premises: 156 PRINCE STREET MANHATTAN BIN: 1007732     Block: 502   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 156 PRINCE ST Census Tract:   49 Health Area:  6800
ELEVATOR MACHINE ROOM & PIT Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   WEST BROADWAY,    THOMPSON STREET
Status:   C - JOB IS SIGNED OFF 07/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/24/2017 8:55 AM
Application Entered:   06/24/2017 Job Start Date:   06/25/2017
Last Change:   07/20/2018 Job End Date:   06/25/2018
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     06/13/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012128 Licensee Name: JOHN DICAPUA
Firm: 003833 Firm Name: CAPUTEK ELEC'L SERVICES,
Firm Phone: 718-610-9299  Firm Address: 1460 BROADWAY, 7TH FLOOR INC NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   D9-ELEVATOR APT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: VILLAGE DWELLINGS, INC
Authorized Representative:  GIRO DESIMONE
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  1P25664
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/23/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  MODERNIZATION OF (1) PASSENGER ELEVATOR, 1P25664 SCOPE OF WORK DIRECTLY RELATED TO ELEVATOR PERMIT. WORK IS LIMITED TO POWER AND LIGHT IN THE ELEVATOR PIT AND MACHINE ROOM ONLY.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M397754
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/13/2018 02/13/2018 CBK N (35) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(2) 02/22/2018 02/23/2018 STP V (50) (6)
INSPECTION COMMENTS: FAIL. 1P25664
 
(3) 06/13/2018 06/13/2018 TOR C R (15) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M397754
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) PIT GFI NOT PROVIDED 620.24
RSLV 02/22/2018 02/22/2018 06/13/2018
 
002 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ROOF) HOISTWAY GFI NOT TRIPPING 110.3
RSLV 02/22/2018 02/22/2018 06/13/2018
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ROOF) MOTOR DISCONNECT AND PANEL 110.12
RSLV 02/22/2018 02/22/2018 06/13/2018
 
004 (999) OTHER
(ROOF) EMT STRAPS USED OUTDOORS 110.3
RSLV 02/22/2018 02/22/2018 06/13/2018
 
005 (999) OTHER
(ROOF) EGC LANDED ON NEUTRAL BAR PANEL 250.24
RSLV 02/22/2018 02/22/2018 06/13/2018
 
006 (999) OTHER
(ROOF) CONDULET COVER LOAD SIDE TO MOTOR FROM CONTROLLER 314.25
RSLV 02/22/2018 02/22/2018 06/13/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.