| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
4 |
ELEVATORS |
| B. Each Additional 10 Floors Or Less |
4 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (BASEMENT) DISCONNECT DOOR NOT FULLY OPEN TO 90 DEGREES. ART 110.26 |
RSLV |
03/15/2019 |
03/15/2019 |
04/04/2019 |
| |
| 002 |
(271) |
BONDING INSUFFICIENT, OVER 250 VOLTS (ROOF)TRANSFORMER BONDING NOT SUFFIENT FOR OVER 250 VOLTS. ART. 250.97 |
RSLV |
03/15/2019 |
03/15/2019 |
04/09/2019 |
| |
| 003 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ROOF) KO IS MISSING IN DISCONNECT. ART. 110.12 |
RSLV |
03/15/2019 |
03/15/2019 |
04/04/2019 |
| |
| 004 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) EMT NOT SUPPORTED. ART. 358.30 |
RSLV |
03/15/2019 |
03/15/2019 |
04/04/2019 |
| |
| 005 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE (ALL FLOORS) CONTROLLERS 277/480 VOLTS 300.12 250.96 |
RSLV |
04/04/2019 |
04/04/2019 |
04/17/2019 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) TRANSFORMER XO NOT BONDED 250.30 |
RSLV |
04/04/2019 |
04/04/2019 |
04/09/2019 |
| |
| 007 |
(302) |
ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED (ROOF) 620.82, ELEVATOR CONTROLLER EQUIPMENT NOT BOND PROPERLY. |
RSLV |
04/09/2019 |
04/09/2019 |
04/17/2019 |
| |
| 008 |
( 41) |
LOCKNUTS ARE NOT MADE UP TIGHT (ROOF) 300.11, LOCK NUT NOT INSTALL AT CONTROLLER. |
RSLV |
04/09/2019 |
04/09/2019 |
04/17/2019 |
| |
| 009 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) 358.30, CONDUIT INSTALL AT CONTROLLER NOT SUPPORTED. |
RSLV |
04/09/2019 |
04/09/2019 |
04/17/2019 |
| |
| 010 |
(999) |
OTHER (ROOF) 348.60, FMC INSTALL BONDING JUMPER REQUIRE. |
RSLV |
04/09/2019 |
04/09/2019 |
04/17/2019 |