Electrical Application Details for App #: M397569
Premises: 338 WEST 36 STREET MANHATTAN BIN: 1090378     Block: 759   Lot: 61
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 338 W 36TH ST Census Tract:   111 Health Area:  5500
ALL FLOORS SERVED,MR Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10018 Community Board:   104
Related Job Number:    121192066
DOB Cross Street(s):    8 AVENUE,    9 AVENUE
Status:   C - JOB IS SIGNED OFF 04/17/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/20/2017 9:42 PM
Application Entered:   06/20/2017 Job Start Date:   06/30/2017
Last Change:   04/17/2019 Job End Date:   06/30/2020
Appointment Status:   
Last Inspection By:   GARY MCCALLA       On     04/17/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011986 Licensee Name: ANTHONY LUCIANO
Firm: 003652 Firm Name: JAM ELECTRICAL CORP
Firm Phone: 212-265-0142  Firm Address: 1133 6TH AVE 28TH FLOOR NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $872.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: YOEL SCHIMMER
Owner Business Name: 338 W 36 LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  4  ELEVATORS
B. Each Additional 10 Floors Or Less  4  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/09/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION OF ELEVATOR BY ELEVATOR COMPANY IN CONJUNCTIONWITH ELEVATOR APPLICATION(273018E). ELEVATOR CONTROL AND LOAD SIDE WIRING ONLY BY ELEVATOR EMPLOYEES CONFORMING TO STANDARDS OF THE ELECTRICAL CODE. POWER TO CONTROL, 110V LIGHTING, MR, PIT GFCI BY OTHERS. ROT-186

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M397569
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/15/2019 03/15/2019 MJD V (115) (4)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETED. OBJECTION ISSUED.
 
(2) 04/04/2019 04/04/2019 STP V Y (60) (2)
INSPECTION COMMENTS: FAIL.
 
(3) 04/09/2019 04/09/2019 DWB V Y (55) (4)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(4) 04/17/2019 04/17/2019 GYM C R (60) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: M397569
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) DISCONNECT DOOR NOT FULLY OPEN TO 90 DEGREES. ART 110.26
RSLV 03/15/2019 03/15/2019 04/04/2019
 
002 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(ROOF)TRANSFORMER BONDING NOT SUFFIENT FOR OVER 250 VOLTS. ART. 250.97
RSLV 03/15/2019 03/15/2019 04/09/2019
 
003 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ROOF) KO IS MISSING IN DISCONNECT. ART. 110.12
RSLV 03/15/2019 03/15/2019 04/04/2019
 
004 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) EMT NOT SUPPORTED. ART. 358.30
RSLV 03/15/2019 03/15/2019 04/04/2019
 
005 ( 40) LOCKNUTS ARE MISSING OR LOOSE
(ALL FLOORS) CONTROLLERS 277/480 VOLTS 300.12 250.96
RSLV 04/04/2019 04/04/2019 04/17/2019
 
006 (999) OTHER
(ALL FLOORS) TRANSFORMER XO NOT BONDED 250.30
RSLV 04/04/2019 04/04/2019 04/09/2019
 
007 (302) ELEVATOR MOTORS/CONTROLLERS/ENCLOSURES NOT GROUNDED
(ROOF) 620.82, ELEVATOR CONTROLLER EQUIPMENT NOT BOND PROPERLY.
RSLV 04/09/2019 04/09/2019 04/17/2019
 
008 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
(ROOF) 300.11, LOCK NUT NOT INSTALL AT CONTROLLER.
RSLV 04/09/2019 04/09/2019 04/17/2019
 
009 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) 358.30, CONDUIT INSTALL AT CONTROLLER NOT SUPPORTED.
RSLV 04/09/2019 04/09/2019 04/17/2019
 
010 (999) OTHER
(ROOF) 348.60, FMC INSTALL BONDING JUMPER REQUIRE.
RSLV 04/09/2019 04/09/2019 04/17/2019