BIS Menu  |  Elev. Device Details  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M397159
Premises: 194 1 AVENUE MANHATTAN BIN: 1005971     Block: 439   Lot: 7
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 194 1ST AV Census Tract:   34 Health Area:  6200
1ST/1/2/3/4/5 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):   EAST 11 STREET,    EAST 12 STREET
Status:   C - JOB IS SIGNED OFF 06/05/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/09/2017 1:39 PM
Application Entered:   06/09/2017 Job Start Date:   08/09/2017
Last Change:   06/05/2018 Job End Date:   08/09/2018
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     02/28/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012361 Licensee Name: ANGELO DOMINGUEZ
Firm: 004263 Firm Name: ALLTECH ELECL CONTNG CORP
Firm Phone: 646-491-2088  Firm Address: 227 SEA BREEZE AVE., STE 201 BROOKLYN NY 11224 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $460.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 192-4 1ST AVE NPG LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  8  20 CKTS.
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  8  SINGLE PHASE 100 AMPS
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF                     
Buildings Total                       
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/18/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THIS PERMIT IS TO ADD ON TO PERMIT #M395871. WE ARE ADDING 8 SINGLE PHASE DISCONNECTS AND 8 CONDENSERS UNITS TO THE ROOF. THIS IS ALSO ADDING 8 SINGLE PHASE MAIN LUG PANELS TO THEAPARTMENTS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M397159
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/15/2017 09/18/2017 CLC V (30) (2)
INSPECTION COMMENTS: INSPECTION FAIL
 
(2) 11/13/2017 11/14/2017 BMP J R (65) (3)
INSPECTION COMMENTS: OBJECTIONS REMOVED. NEW OBJECTIONS NOTED. JOB IN PROGRESS. FAIL.
 
(3) 02/28/2018 03/01/2018 TOR C R (5) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M397159
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 005)TOP FL APTS AC UNITS SPLICE BOXES NOT ACCESSIBLE 300.15 A
RSLV 09/15/2017 09/15/2017 11/13/2017
 
002 (999) OTHER
(ROOF) ROOF GFCI NOT WR 406.8 A
RSLV 09/15/2017 09/15/2017 11/13/2017
 
003 (999) OTHER
(ROOF)ROOF. SEC. 350.6 AND 350.120. LFMC TO ROOFTOP ACS NOT LISTED(?) ANDNOT MARKED OR IDENTIFIED.
RSLV 11/13/2017 11/13/2017 02/28/2018
 
004 (999) OTHER
(ROOF) ROOF. SEC. 310.15(B)(2) AND 110.3(B). DERATED VALUE OF #8 CU,SINGLE-PHASE, 3-WIRE BRANCH CIRCUITS TO ROOFTOP ACS DOES NOT MEETNAMEPLATE "MINIMUM" CIRCUIT AMPACITY.
RSLV 11/13/2017 11/13/2017 02/28/2018
 
005 (999) OTHER
(ROOF) SEC. 350.12 AMENDMENT. LFMC LENGTHS IN EXCESS OF 6 FT.
RSLV 11/13/2017 11/13/2017 02/28/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.