Electrical Application Details for App #: M397107
Premises: 301 EAST 40 STREET MANHATTAN BIN: 1038645     Block: 1333   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 305 E 40TH ST Census Tract:   88 Health Area:  5000
APT 17 J AND 17 K & 17 J Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):    2 AVENUE,    QUEENS MIDTOWN TUNNEL APPROACH
Status:   C - JOB IS SIGNED OFF 10/05/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/08/2017 11:55 AM
Application Entered:   06/08/2017 Job Start Date:   06/08/2017
Last Change:   10/05/2018 Job End Date:   11/20/2017
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     02/05/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011804 Licensee Name: JAMAL DUDLEY
Firm: 003415 Firm Name: DUDLEY & ASSOC. LIC. ELEC
Firm Phone: 718-588-2822  Firm Address: 6 EAST CLARK PLACE CONTR., INC. BRONX NY 10452 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $310.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CAROLYN SABBA
Owner Business Name: SABBA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  4  15 AMOS
C. 201 Up to 600 AMPS  1  30 AMPS
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  12/24
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
017  17 FL  22  32    16               
Buildings Total 22  32    16                  
Total Units : 70 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/18/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REWIRING OF APT 17 (K) & 17 (J).$ DEDICATED LINES 120V 15 AMPS FOR DISHWASHER, REFRIGERATOR. MICROWAVE & 2 DISHWASHERS.3 MOTION DETECTORS FOR CLOSET AND 3 T/V OUTLETS, 2 PANEL BREAKERS ONE T TO REMOVE AND ONE FUSE BOX TO CHANGE BREAKER 12/14.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M397107
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/28/2017 11/28/2017 TUR N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW ,
 
(2) 12/11/2017 12/12/2017 CBK N (39) (0) Y
INSPECTION COMMENTS: NO SHOW.
 
(3) 01/18/2018 01/18/2018 CBK V (60) (3)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(4) 02/05/2018 02/05/2018 VTC C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M397107
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 58) FIXTURE NOT PROPERLY LOCATED IN CLOTHES CLOSET
(FLOOR: 017) OPEN BULB IN ALL CLOSETS.
RSLV 01/18/2018 01/18/2018 02/05/2018
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 017) NOT ALL REQUIRED CIRCUIT IS AFCI PROTECTED.
RSLV 01/18/2018 01/18/2018 02/05/2018
 
003 (999) OTHER
(FLOOR: 017)20A INDIVIDUAL CIRCUIT NEED 20A RECEPTACLE. 210.21(B)(1)
RSLV 01/18/2018 01/18/2018 02/05/2018