Electrical Application Details for App #: M396969
Premises: 20 HUDSON YARDS MANHATTAN BIN: 1088961     Block: 702   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 500 W 33RD ST Census Tract:   99 Health Area:  5500
1,6 10, 11, 23, 79 FL Admin Area:   M - MANHATTAN Inspection Area:   Q
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   HUDSON YARDS TOWER A
DOB Cross Street(s):    10 AVENUE,    HUDSON BOULEVARD EAST
Status:   C - JOB IS SIGNED OFF 06/07/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/06/2017 9:22 AM
Application Entered:   06/06/2017 Job Start Date:   06/06/2017
Last Change:   06/07/2024 Job End Date:   02/08/2020
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     06/07/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011556 Licensee Name: MARIAN BRODNANSKY
Firm: 002191 Firm Name: EGG ELECTRIC INC.
Firm Phone: 212-633-9551  Firm Address: 35 WEST 45TH STREET 4TH NEW YORK NY 10036 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
L - LIGHTING WORK
Total Fee:  $5,040.00
Other Work:   INSTALL UPS&BATTERIES
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122999737
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOEL BRENNER
Owner Business Name: TW NY PROPERTIES LLC
Authorized Representative:  JOEL BRENNER
Relationship To Owner:   VICE PRESIDENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  2 #4 1"C, 3 #2 IN 1.25"C
B. Over #2 to 1/0  1  1 SETS #1/0 IN 1.5"C
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  96  96 (3) 600MCM & 350G 4"C
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  12  
D. 3 Phase Over 225 AMPS  16  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      10                30 
006    10            15 
010    48  23    48             
011    43  53    43             
023                      30 
079                30 
Buildings Total 103  96    11  103               105 
Total Units : 418 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/09/2024
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  EGG JOB #2550/2551 TIME WARNER- 30 HUDSON YARDS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M396969
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2024 02/10/2024 DWB V (321) (7)
INSPECTION COMMENTS: ATOI FRANCISCO- INSPECTION INCOMPLETE, 4-2500 AMP MAIN, MDP- PANEL FED FROM FIRST LEVEL 4-2500 AMP1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL AM 110.2B, 79 FLR CONTRACTOR HAVE NO ACCESS, CONTRACTOR TO REFILE APPS FOR MISSING EQUIP AND FEEDERS, OBJECTION ISSUED.
 
(2) 03/09/2024 03/09/2024 VGV V Y (195) (1)
INSPECTION COMMENTS: RESUMED INSPECTION FROM POINT WHERE PREVIOUS INSPECTOR LEFT OFF, ONLY THING NOT CHECKED IS WORK THAT REQUIRES P/R IN 10TH FL. 2500A MDP'S FED FROM OVER 1000KVA SERVICE. CONTRACTOR TO FILE WITH P/R. ATOI MARIAN.
 
(3) 06/07/2024 06/07/2024 GIG C R (69) (0)
INSPECTION COMMENTS: EPR NOT NEEDED CONTRACTORS WORK WAS 3RD LEVEL (5-STAR DID THE SERVICE UP TO SECOND LEVEL, SUM #16A0419 C# 53597) ATOI MARIAN

OBJECTION FOR APPLICATION #: M396969
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 016)FMC 348.30(A-B) SECURING AND SUPPORTING. FMC SHALL BE SECURELYFASTENED IN PLACE AND SUPPORTED/ NOT SUPPORTED INSTALLED ATTRANSFORMER.
RSLV 02/10/2024 02/10/2024 03/09/2024
 
002 (212) NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM
(FLOOR: 016)250.30/ 208/480 TRANSFORMER NOT BONDED BUILDING STEEL/ STRUCTURE ATELE-CLOSET.
RSLV 02/10/2024 02/10/2024 03/09/2024
 
003 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)10.11,16, FLR - WARNING LABELS FOR 277 / 480 VOLT AM408.60(C) NOTPROVIDED/ AT TRANSFORMER, DIS SWITCHES AND PANELS.
RSLV 02/10/2024 02/10/2024 03/09/2024
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)ALL BOXES AND ENCLOSURES (INCLUDING TRANSFER SWITCHES, GENERATORS,AND POWER PANELS), SHALL MARK PERMANENTLY 700.9,/ NOT PROVIDEDTHRU-OUT.
RSLV 02/10/2024 02/10/2024 03/09/2024
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)110.16, ARC FLASH LABEL NOT PROVIDED AT NEW ELECTRICAL EQUIPINSTALLED/ NOT PROVIDED THRU-OUT
RSLV 02/10/2024 02/10/2024 03/09/2024
 
006 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(ALL FLOORS)10,11 FLR- 4-2500 AMP MAIN, MDP- PANEL FED FROM FIRST LEVEL 4-2500AMP1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL AM 110.2B,
RSLV 02/10/2024 02/10/2024 06/07/2024
 
007 (999) OTHER
(ALL FLOORS) CONTRACTOR TO REFILE APPS FOR MISSING EQUIP ANDFEEDERS, FROM APPS M396969.- CONTRACTOR NEED TO ADD, FEEDERS, 129SET OVER 250 MCM, TOTAL 225 SET INSTALLED,- 14 SET UP TO #2, TOTAL23 SET INSTALLED,- FLR DESCRIPTION, 10 AND 11 FLR, MOTORS, TOTAL 21,TOTAL 21 INSTALLED. SEE COMMENT.
RSLV 02/10/2024 02/10/2024 03/09/2024
 
008 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 079)240.21, TABLE 450.3B, 110.3 UNABLE TO VERIFY TRIP SETTING FOR 250AADJUSTABLE MAIN BREAKER PROTECTING #1 AWG SECONDARY CONDUCTORS OFF30KVA XFRMRS
RSLV 03/09/2024 03/09/2024 06/07/2024