Electrical Application Details for App #: M396648
Premises: 4 ST MARKS PLACE MANHATTAN BIN: 1006661     Block: 463   Lot: 11
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 4 SAINT MARKS PL Census Tract:   38 Health Area:  6500
BASE-1-2-3-4 Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
DOB Cross Street(s):    3 AVENUE,    2 AVENUE
Status:   C - JOB IS SIGNED OFF 09/16/2019 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/29/2017 9:38 PM
Application Entered:   05/29/2017 Job Start Date:   05/29/2017
Last Change:   09/16/2019 Job End Date:   04/20/2018
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     05/13/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011485 Licensee Name: BENJAMIN DREBIN
Firm: 002950 Firm Name: ACCURATE ELEC'L CORP.
Firm Phone: 718-606-9181  Firm Address: 11-07 43RD ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $826.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAMIEN SMITH
Owner Business Name: C&R CONTRACTING
Authorized Representative:  DAMIEN SMITH
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  3  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  6  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  6  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    13    13             
001  STOR1  12  12         
001  STOR2  12  12         
002  A-B  18  22  13  18         
003  A-B  18  22  13  18         
004  A-B  18  22  13  18         
005  A-B  18  22  13  18         
Buildings Total 109  109  10  69  109     10           
Total Units : 416 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 6 #4-Wire 3 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/29/2017 Notice: 1 - FIRST NOTICE 02/14/2019
Power Issued: 05/29/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  D1A2M3I5A6N8- BASR-1-2-3-4 FLOOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M396648
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2019 01/29/2019 TOR N (30) (0) Y
INSPECTION COMMENTS: FAIL NO SHOW
 
(2) 02/13/2019 02/14/2019 EDB V (120) (12)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(3) 05/13/2019 05/14/2019 LV1 C R (70) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M396648
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 001) 110.2.3.7 OPEN WIRING IN THE RETAIL STORE
RSLV 02/13/2019 02/13/2019 05/13/2019
 
002 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ALL FLOORS)250.24 PANELS: NEUTRAL BONDED AFTER S. SW.
RSLV 02/13/2019 02/13/2019 05/13/2019
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
(ALL FLOORS) 314.25 OUTLET BOX(S) NOT COVERED
RSLV 02/13/2019 02/13/2019 05/13/2019
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) 314.20,21 GAP BY BATHROOM LIGHTS
RSLV 02/13/2019 02/13/2019 05/13/2019
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)210.12 AFCI PROTECTION MISSING IN THE APARTMENTS
RSLV 02/13/2019 02/13/2019 05/13/2019
 
006 ( 63) RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER
(ALL FLOORS) 210.52 KITCHEN COUNTERTOP MISSING RECEPTACLE
RSLV 02/13/2019 02/13/2019 05/13/2019
 
007 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(CELLAR) 250.24 PLP AND RETAIL # 1 S. SW(S)
RSLV 02/13/2019 02/13/2019 05/13/2019
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) AM. 695.4(A) F/P CONNECTED ON LOAD SIDE OF PLP S. SW.
RSLV 02/13/2019 02/13/2019 05/13/2019
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) AM. 695.6(E) LFMC FOR F/P MOTOR OVER 3'
RSLV 02/13/2019 02/13/2019 05/13/2019
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) AM. 760.41(A) F/A CONNECTED ON LOAD SIDE OF PLP S. SW.
RSLV 02/13/2019 02/13/2019 05/13/2019
 
011 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR)AM. 695.4(B)3(4) DISC. MEANS FOR F/P LESS THAN 12" FROM PLP S.SW.
RSLV 02/13/2019 02/13/2019 05/13/2019
 
012 (999) OTHER
(CELLAR) AM. 695.4(B)4 MARKING AND COLOR OF F/P SW.
RSLV 02/13/2019 02/13/2019 05/13/2019