| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
3 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
6 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
1 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
6 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 001) 110.2.3.7 OPEN WIRING IN THE RETAIL STORE |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 002 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ALL FLOORS)250.24 PANELS: NEUTRAL BONDED AFTER S. SW. |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 003 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) 314.25 OUTLET BOX(S) NOT COVERED |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS) 314.20,21 GAP BY BATHROOM LIGHTS |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 005 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)210.12 AFCI PROTECTION MISSING IN THE APARTMENTS |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 006 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (ALL FLOORS) 210.52 KITCHEN COUNTERTOP MISSING RECEPTACLE |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 007 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (CELLAR) 250.24 PLP AND RETAIL # 1 S. SW(S) |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 008 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) AM. 695.4(A) F/P CONNECTED ON LOAD SIDE OF PLP S. SW. |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 009 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) AM. 695.6(E) LFMC FOR F/P MOTOR OVER 3' |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) AM. 760.41(A) F/A CONNECTED ON LOAD SIDE OF PLP S. SW. |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 011 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR)AM. 695.4(B)3(4) DISC. MEANS FOR F/P LESS THAN 12" FROM PLP S.SW. |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |
| |
| 012 |
(999) |
OTHER (CELLAR) AM. 695.4(B)4 MARKING AND COLOR OF F/P SW. |
RSLV |
02/13/2019 |
02/13/2019 |
05/13/2019 |