| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005) 5D APT PENDANT LIGHT NOT GROUNDED ART. 410.40 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 002 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005) APT. 5D BOX NOT SUPPORTED T-OUT ART. 314.25 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 003 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005) APT 5D OPEN SPLICES ,ART. 300.15 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 004 |
(145) |
APPLIANCE DISCONNECT NOT PROVIDED/IDENTIFIED. (ALL FLOORS)KITCHEN APPLIANCES NO DISCONNECTS T-OUT ART.422.30, 422.31 |
RSLV |
02/19/2022 |
02/19/2022 |
05/09/2022 |
| |
| 005 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)ALL AIR HANDLERS FUSED NOT AS PER MANUF. SPEC. 15 AMP MAX , FUSED 20AMP ART. 110.2 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 006 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)NO ACCESS TO THE 8 FLOOR APTS. ,5B,5A, 4 FLOOR NO ACCESS TO THEAPTS. 2A,2B NO ACCESS. |
RSLV |
02/19/2022 |
02/19/2022 |
05/09/2022 |
| |
| 007 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) PANEL HANDLE TIES NOT PROVIDED T-OUT ART.210.4B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 008 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) ARC FLASH LABELS NOT PROVIDED ART, 110.16 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 009 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) PANEL DIRECTORY MISSING T-OUT ART.408.4 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 010 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) APT 11 PH A UNDER CONSTRUCTION |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 011 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) GFCI NOT TR TYPE T-OUT ART. 406.11 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 012 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) HEAT TRACE NOT GFPE PROTECTED, ART.427.22 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 013 |
(284) |
NO OUTLET FOR KITCHEN ISLAND (ALL FLOORS) KITCHEN ISLAN GFCI LOCATION ART.210.52C2 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 014 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS) KITCHEN ISLAND GFCI NOT PROVIDED T-OUT ART 210.8 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 015 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ALL FLOORS)MEDICINE CABINET OUTLET NOT GFCI PROTECTED T-OUT ART 210.8 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 016 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)AFCI NOT PROVIDED FOR ALL LISTED AREAS T-OUT ART 210.12B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 017 |
(999) |
OTHER (ALL FLOORS)CONTRACTOR NEEDS TO OPEN NEW APP TO CORRECT QUANTITY OF SERCVICESWITCHES , HEATERS , MOTORS, ETC. AND CORRECT SCOPE OF WOR SAME APTRENOWATED UNDER NEW APPS BY DIFERENT CONTRACTORS. |
RSLV |
02/19/2022 |
02/19/2022 |
05/09/2022 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES ART.250.122 , 110.2, 314.25,320.15 |
RSLV |
02/19/2022 |
02/19/2022 |
05/09/2022 |
| |
| 019 |
(126) |
BASEMENT WATER MAIN GROUND NOT INSTALLED ON WATER MAIN (CELLAR) WATER MAIN GROUND NOT INSTALLED ON WATER MAIN ART 250 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 020 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (CELLAR) CONSTRUCTION TEMP NOT REMOVED T-OUT ART. 590.3D |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 021 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (CELLAR) APT 9 400 AMP DISCONNECT WIRES OVER FUSED . ART 310.16 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 022 |
(192) |
CONDUCTORS ARE OVER FUSED AS PER TABLE 310.16 (CELLAR) GARBAGE COMPACTOR WIRE OVER FUSED #12 ON 30 AMP ART. 310.16 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 023 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (CELLAR) GARBAGE COMPACTOR GROUND UNDER SIZED. ART. 250.122 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 024 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) WATER POMP FUSE NOT AS PER AB DRAWING ART. AM 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 025 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) RDB WIRE SETS NOT AS PER AB DRAWINGS ART. AM 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 026 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) HDB SECTION 2 , NOT AS PER AB DRAWINGS ART. AM. 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 027 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) SS#4 FUSE NOT AS PER AB DRAWINGS. ART.AM 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 028 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)APT 9 400 AMP DISCONNECT FUSE NOT AS PER AB DRAWINGS ART. AM 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 029 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (CELLAR)JOCKEY PUMP CONNECTION (CONTRACTOR CANT FIND CONNECTION ) ART.110.2 314.29 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 030 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ROOF)GENERATOR BREAKERS SIZE NOT AS PER AB DRAWINGS ART.AM 110.2B |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 031 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (ROOF) ROOF OUTLET REQUIRED HVAC EQUIPMENT ART. 210.63 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 032 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ROOF) ROOF ATS ROOM EMT NOT SUPPORTED. ART. 358.30 |
RSLV |
02/19/2022 |
02/19/2022 |
05/02/2022 |
| |
| 033 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (FLOOR: 005) DEFECTIVE LIGHT FIXTURE IS IN USE. 110.2 A |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 034 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (FLOOR: 008)APT 8 D FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD KITCHEN.400.8 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 035 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008)APT 8 D 8 A 8 B, DRYER OUTLET GROUND UNDERSIZED T-OUT. 250.122 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 036 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008)APT 8 D, FLEXIBLE CORDS MAY BE USED FOR CONNECTION OF APPLIANCESIDENTIFIED HOOD DISCONNECT. 400.7 8 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 037 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 008)BOX SET BACK MORE THAN INTO COMBUSTIBLE MATERIAL. ART 314.20 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 038 |
( 29) |
OUTLET BOXES ARE NOT COVERED (FLOOR: 008) APT 8 D, SPLICE BOX OPEN IN KITCHEN CABINET. 314.25 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 039 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 008)APT 8 A, B AFCI PROTECTION NOT PROVIDED IN ALL AREAS LISTED T-OUT.210.12 B |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 040 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 008) AFCI PROTECTION NOT PROVIDED IN LISTED AREAS. 210.12 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 041 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)STEAM UNIT DISCONNECT NOT LABEL / MARKED ABOVE CEILING T-OUT. 110.22 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 042 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)NO MANUFACTURER LABEL AND LISTING FOR STEAM UNIT ABOVE CEILING /EQUIPMENT. 110.2 |
RSLV |
05/02/2022 |
05/02/2022 |
05/09/2022 |
| |
| 043 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 005) APT 5D HALLWAY OUTLET NOT WORKING ART.110.2 |
RSLV |
05/09/2022 |
05/09/2022 |
05/11/2022 |
| |
| 044 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 011)APT 11A KITCHEN ISLAND OUTLETS NOT GFCI PROTECTED ART.210.8 |
RSLV |
05/09/2022 |
05/09/2022 |
05/11/2022 |
| |
| 045 |
(999) |
OTHER (ALL FLOORS)AFFIDAVIT FOR ALL KITCHEN APPLIANCES NO ACCESS TO THE WIRING T-OUTART.250.122, 314.25, 320.40, 422.30, 300.15,110.2 |
RSLV |
05/09/2022 |
05/09/2022 |
05/11/2022 |