BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M396259
Premises: 1049 PARK AVENUE MANHATTAN BIN: 1047971     Block: 1515   Lot: 70
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1049 PARK AV Census Tract:   148.02 Health Area:  3600
LOBBY Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 86 STREET,    EAST 87 STREET
Status:   C - JOB IS SIGNED OFF 08/01/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/17/2017 9:36 PM
Application Entered:   05/17/2017 Job Start Date:   05/29/2017
Last Change:   08/01/2017 Job End Date:   06/20/2017
Appointment Status:   
Last Inspection By:   MODELFINO, CARL C       On     07/31/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012152 Licensee Name: EDIN BECIROVIC
Firm: 003854 Firm Name: NEW KC ELECTRIC INC
Firm Phone: 718-392-0077  Firm Address: 36-32 23 STREET LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $42.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: GUMLEY HAFT, INC
Authorized Representative:  EDITH  SCHICKEDANZ
Relationship To Owner:   PROPERTY MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB                   
Buildings Total                   
Total Units : 18 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/19/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING ADDITIONAL CEILING AND WALL MOUNTED LIGHTING FIXTURES AND SWITCHES ONLY

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M396259
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/19/2017 07/19/2017 MQY V (90) (2)
INSPECTION COMMENTS: NEUTRAL IS BEING FAKED OFF OF THE EGC OF THE SPLICE BOX
 
(2) 07/31/2017 08/01/2017 MLF C R (24) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED

OBJECTION FOR APPLICATION #: M396259
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(GROUND FLOOR)NEUTRAL IS DERIVED FROM THE SPLICE BOX ENCLOSURE (LIGHTS FLICKERWITH A SLIGHT TOUCH)LIGHTS ARE FUNCTIONING WITH THE NEUTRAL COMINGFROM THE EQUIPMENT GROUNDING (250.24)
RSLV 07/19/2017 07/19/2017 07/31/2017
 
002 (999) OTHER
(GROUND FLOOR) NEW MC CABLE EGC NOT BONDED IN BOXES (250.148)
RSLV 07/19/2017 07/19/2017 07/31/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order