| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
NEW FEEDERS. |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| SUB FEEDERS (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
8 |
#2 CU, SINGLE-PHASE, 3-WI |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
8 |
100A, 20CKTS. |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (FLOOR: 005) KITCHENS MISSING GFCI COUNTERTOP 210.8 |
RSLV |
06/15/2017 |
06/15/2017 |
09/15/2017 |
| |
| 002 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED (ROOF) FLEXIBLE METAL CONDUITS HVAC. |
RSLV |
06/15/2017 |
06/15/2017 |
09/15/2017 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 003) APT 4 PANEL FEEDER CONNECTOR NOT GNDED TO BOX |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 004 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 003) APT 3 PANEL CONNECTORS MISSING |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 005) AC UNITS MC CABLE GROUND NOT BONDED TO BOXES 250.118 |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 006 |
(999) |
OTHER (FLOOR: 005) SLPICE BOXES FOR AC UNITS NOT ACCESSIBLE 300.15 A |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 007 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) KO MISSING IN PANELS THOUGH OUT APTS |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 008 |
(340) |
RECEPTACLES NOT TAMPERPROOF (ALL FLOORS) KITCHEN COUNTER GFCI THOUGH OUT NOT TR 406.11 |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 009 |
(999) |
OTHER (ROOF) ROOF GCFI NOT WR 406.8 A |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |
| |
| 010 |
(999) |
OTHER (ROOF) ROOF SEAL TIGHT SUPPORTS NOT APPROVED 350.30 A |
RSLV |
09/15/2017 |
09/15/2017 |
11/13/2017 |