Electrical Application Details for App #: M395816
Premises: 196 MOTT STREET MANHATTAN BIN: 1007159     Block: 479   Lot: 9
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 196 MOTT ST Census Tract:   41 Health Area:  6800
5TH FL Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   KENMARE STREET,    SPRING STREET
Status:   C - JOB IS SIGNED OFF 05/10/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/09/2017 11:00 AM
Application Entered:   05/09/2017 Job Start Date:   05/10/2017
Last Change:   05/10/2018 Job End Date:   04/30/2018
Appointment Status:   
Last Inspection By:   RILEY (MONTY) MONTAGUE       On     05/04/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $62.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   APARTMENT BUILDING
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KA WO SZETO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CK MAIN LUG
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
005  28  15             
Buildings Total 15                
Total Units : 38 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/14/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395816
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/20/2017 07/20/2017 CBK J (34) (0) Y
INSPECTION COMMENTS: JOB NOT READY FOR INSPECTION, WALLS OPEN.
 
(2) 11/16/2017 11/17/2017 CBK V (45) (6)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(3) 01/18/2018 01/19/2018 TOR J Y (30) (0)
INSPECTION COMMENTS: FAIL
 
(4) 03/13/2018 03/14/2018 CBK J X (35) (0) Y
INSPECTION COMMENTS: OBJECTION NOT RESOLVED.
 
(5) 05/04/2018 05/09/2018 MYT C R (60) (0)
INSPECTION COMMENTS: JOB CERTIFIED

OBJECTION FOR APPLICATION #: M395816
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 19) DEFECTIVE WIRING IS IN USE
(FLOOR: 005) BX SPLICE TO FLEX CORD (FOR HOOD) WITHOUT BOX.
RSLV 11/16/2017 11/16/2017 01/18/2018
 
002 (211) RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED
(FLOOR: 005) NONE GROUNDED TYPE RECEPTACLES ARE NOT PROPERLY BONDED.
RSLV 11/16/2017 11/16/2017 01/18/2018
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 005) NO PANEL DIRECTORY.
RSLV 11/16/2017 11/16/2017 01/18/2018
 
004 (999) OTHER
(FLOOR: 005) NO AC RECEPTACLE PROVIDED. 210.52(I) AMEN.
RSLV 11/16/2017 11/16/2017 01/18/2018
 
005 (999) OTHER
(FLOOR: 005) MINIMUM 2 COUNTER TOP CIRCUITS.
RSLV 11/16/2017 11/16/2017 05/04/2018
 
006 (999) OTHER
(FLOOR: 005) NO RECEPTACLE PROVIDED IN THE BATHROOM. 210.52(5)(D)
RSLV 11/16/2017 11/16/2017 01/18/2018