NYC Department of Buildings
Electrical Application Details for App #: M395812
Premises: 212 BROADWAY MANHATTAN BIN: 1001245     Block: 89   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 147 FULTON ST Census Tract:   15.01 Health Area:  7700
1ST FLOOR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   NASSAU STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 01/10/2023
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/09/2017 10:47 AM
Application Entered:   05/09/2017 Job Start Date:   05/09/2017
Last Change:   01/10/2023 Job End Date:   05/09/2018
Appointment Status:   
Last Inspection By:   RIVERA, F       On     01/09/2023      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012551 Licensee Name: JAMES T MAXWELL
Firm: 004370 Firm Name: CROSSTOWN ELECL CONTRS IN
Firm Phone: 347-527-2007  Firm Address: 37-31 58TH STREET WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $354.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: L&L HOLDING COMPANY LLC
Authorized Representative:  DAVID BERK
Relationship To Owner:   PROPERTY MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  (2SET)4#3/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  (2) 200A
D. 3 Phase Over 225 AMPS  1  (1) 600A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    110  70    13  110  25         
Buildings Total 110  70    13  110     25           
Total Units : 328 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/05/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395812
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/04/2017 12/05/2017 PHG V (40) (4)
INSPECTION COMMENTS: FOR FEEDERS OF 600 AMP PANEL REFER TO APP M396540. INSPECTED PANELS AND FEEDERS ONLY
 
(2) 01/09/2023 01/10/2023 FRI C R (1) (0)
INSPECTION COMMENTS: SUPERSEDED BY # M00613558

OBJECTION FOR APPLICATION #: M395812
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(GROUND FLOOR) NO 90 SWING FOR FIRE ALARM 110.26
RSLV 12/04/2017 12/04/2017 01/09/2023
 
002 (125) PROTECTION OF CONDUCTORS NOT INSTALLED AS PER CODE
(GROUND FLOOR) 8 WIRE TAPED FROM 600 AMP FUSE TO FIRE ALARM 240.21
RSLV 12/04/2017 12/04/2017 01/09/2023
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(GROUND FLOOR) NOT ALL 120V OUTLETS GFCI PROTECTED IN KITCHEN 210.8
RSLV 12/04/2017 12/04/2017 01/09/2023
 
004 (999) OTHER
(GROUND FLOOR) IMPROPER TAP FROM PARALLEL SET 310.4
RSLV 12/04/2017 12/04/2017 01/09/2023