Electrical Application Details for App #: M395811
Premises: 5 BEEKMAN STREET MANHATTAN BIN: 1079072     Block: 90   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 5 BEEKMAN ST Census Tract:   15.01
ALL FLOORS Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Related Job Number:    121329268
DOB Cross Street(s):   THEATER ALLEY,    NASSAU STREET
Status:   C - JOB IS SIGNED OFF 02/23/2022
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   05/09/2017 Job Start Date:   05/09/2017
Last Change:   02/23/2022 Job End Date:   03/09/2018
Appointment Status:   
Last Inspection By:   GIUSEPPE IMBURGIA       On     02/05/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011437 Licensee Name: ANTONY GIRONTA
Firm: 002894 Firm Name: AGIR ELEC'L LTD. D/B/A
Firm Phone: 718-846-6200  Firm Address: 130-45 91ST AVENUE PINNACLE ELECTRICAL RICHMOND HILL NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $5,040.00
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121329268
Building Used As:   Z - Other
Store / Other:   HOTEL & CONDO
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52960     Submittal #: 14A0318  
Owner / Occup: STEVEN HURWITZ
Owner Business Name: BROADWAY CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  100 AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  800 AMPS
E. Over 1200 AMPS  6  2-4000, 4-3000
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  1-4#2
B. Over #2 to 1/0  72  72-3#1/0
C. Over 1/0 to 250 MCM  20  20-4#4/0
D. Over 250 MCM  20  750 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  72  
C. 3 Phase Up to 225 AMPS  20  
D. 3 Phase Over 225 AMPS  20  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  30  15  16          750 
001    20  30  15  16          500 
002    20  30  15  16          100 
003    20  30  15  16             
004    20  30  15  16             
005    20  30  15  16             
006    20  30  15  16             
007    20  30  15  16             
008    20  30  15  16             
009    20  30  15  16             
010    20  30  15  16             
011    20  30  15  16             
012    20  30  15  16  500         
013    20  30  15  16             
014    20  30  15  16             
015    20  30  15  16             
016    20  30  15  16             
017    20  30  15  16             
018    20  30  15  16             
019    20  30  15  16             
020    20  30  15  16             
021    20  30  15  16             
022    20  30  15  16             
023    20  30  15  16             
024    20  30  15  16             
025    20  30  15  16             
026    20  30  15  16             
027    20  30  15  16          750 
028    20  30  15  16          500 
029    20  30  15  16          100 
030    20  30  15  16             
031    20  30  15  16             
032    20  30  15  16             
033    20  30  15  16             
034    20  30  15  16             
035    20  30  15  16             
036    20  30  15  16             
037    20  30  15  16             
038    20  30  15  16             
039    20  30  15  16             
040    20  30  15  16             
041    20  30  15  16             
042    20  30  15  16             
043    20  30  15  16             
044    20  30  15  16             
045    20  30  15  16             
046    20  30  15  16             
048    20  30  15  16             
049    20  30  15  16             
050    20  30  15  16             
ROF    20  30  15  16  120         
Buildings Total 1020  1530  255  765  816     620          2700 
Total Units : 7706 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 72 #4-Wire 3 #10-Wire 6
Existing Meters 0 + New Meters 81 - Removed Meters 0 = Total Meters 81

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/09/2017 Notice: 1 - FIRST NOTICE 01/08/2022
Power Issued: 05/09/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRE FOR LIGHTS AND POWER WITH 2 SERVICESGENERATOR (4 POLE) 12TH FLOOR. REMOVE ECB 35228346X 35228347H 35228348J 35228349L 35228441J

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395811
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/20/2018 10/23/2018 TUR V (315) (22)
INSPECTION COMMENTS: OBJECTIONS ISSUED , SEE OBJECTION NOTES , NEED COMPLETE INSPECTION OF AREAS
 
(2) 08/21/2021 08/23/2021 CDX V Y (360) (28)
INSPECTION COMMENTS: FAIL. ATOI JOE BEST . INCOMPLETE INSPECTION. INSPECTED ADVISOR BOARD ONLY C 52960 SUB 14A0318. USED CONTRACTOR DRAWING ONE LINE DRAWING. NO ACCESS TO INSPECT JOCKEY PUMP TAP FLOOR 32 TH . REF APP M00577224I1EL AMENDED 1150 KW GENERATOR TO APP
 
(3) 01/08/2022 01/08/2022 GIG V R (390) (2)
INSPECTION COMMENTS: SELF CERTIFY SEE OBJECTIONS ALSO SEE APP. M00577224 INSPECTION COMPLETE
 
(4) 02/05/2022 02/05/2022 GIG C R (50) (0)
INSPECTION COMMENTS: INSPECTION PASSED ALSO SEE APP. M00577224

OBJECTION FOR APPLICATION #: M395811
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS)408.4 PANELS IN ALL AREAS DO NOT HAVE DIRECTORIES (THRU OUTINFRASTRUCTURE , HOTEL AND RESIDENCE )
RSLV 10/20/2018 10/20/2018 01/08/2022
 
002 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(ALL FLOORS)210.12(B) CAFCI BREAKERS MISSING IN ALL CONDOS NEED DIRECTORIES TOSHOW ACCURATE MISSING CBS (SEE ALL LISTED IN CODE SECTION )
RSLV 10/20/2018 10/20/2018 01/08/2022
 
003 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
(ALL FLOORS)430.75 NO ACCESS OR NO DISCONNECT PROVIDED FOR ALL UNITS MOUNTED INCEILINGS OF THE CONDOS NEED RATING FOR SPEC FOR BREAKER SIZING
RSLV 10/20/2018 10/20/2018 01/08/2022
 
004 (999) OTHER
(ALL FLOORS)406.8(B) ALL OUTDOOR GFCI NEED WR TYPE AND IN USE COVERS ROOF TO THEBOTTOM
RSLV 10/20/2018 10/20/2018 01/08/2022
 
005 (999) OTHER
(ALL FLOORS)BEFORE SCHEDULING ANOTHER APPOINTMETN CONTACT TUR IN MANHATTANOFFICE TO GO OVER THE APPLICATIONS SUBMITTED AND AMENDED
RSLV 10/20/2018 10/20/2018 01/08/2022
 
006 (999) OTHER
(ALL FLOORS)NOTE 6 RESTAURANT NOT INSPECTED WINDOW FOR INSPECTION BETWEEN 3 AND5
RSLV 10/20/2018 10/20/2018 01/08/2022
 
007 (999) OTHER
(ALL FLOORS)314.20 OUTLETS SET BACK IN HITCHEN AREA BACKSPLASHES AND RELATEDSTONE (ALSO SEE BATHROOMS MORE THAN CODE ALLOWED 1/4" CHECK ALLOUTLETS FOR BONDING
RSLV 10/20/2018 10/20/2018 01/08/2022
 
008 (999) OTHER
(ALL FLOORS) DISCONNECT NOT PROVIDED FOR STEAM GENERATOR ALL CONDOS
RSLV 10/20/2018 10/20/2018 01/08/2022
 
009 (999) OTHER
(ALL FLOORS)332. MI CABLE NOT INSTALLED AS PER CODE ARTICLE THRU OUT
RSLV 10/20/2018 10/20/2018 01/08/2022
 
010 (999) OTHER
(ALL FLOORS)NOTE 5: MUST GET A FULL COUNT OF PANELS, FEEDERS, SERVICE FEEDERS,TRANSFORMERS , ETC AND ADD MISSING TO THE NEW APP.
RSLV 10/20/2018 10/20/2018 01/08/2022
 
011 (999) OTHER
(ALL FLOORS)314.20 OUTLETS IN ALL MILL AND BASE MOLDING (GYMS, HOTEL ROOMS,HALLS, LOBBY AREAS IN STONE THRU OUT SET BACK MORE THAN 3INCHES INSOME AREAS EXTENSION COLLAR AND SLEEVE NEED GYM AREAS ALL BASE INHOTEL ROOMS NEED FULL ADAPTER FOR 2INCHES
RSLV 10/20/2018 10/20/2018 01/08/2022
 
012 (999) OTHER
(ALL FLOORS)NOTE 4: DURING INSPECTION ONLY INSPECTED 4 CONDOS NO ACCESS TOOTHERS AT TIME OF INSPECTION ONLY INSPECTED 5 HOTEL ROOMS MOTE TO BEINSPECTED IN BOTH AREAS , DID NOT INSPECT RESTAURANTS AND RELATEDAREAS
RSLV 10/20/2018 10/20/2018 01/08/2022
 
013 (999) OTHER
(ALL FLOORS)110.26 ALL ELECTRICAL ROOMS TRU OUT TO BE INSPEECTED WHEN STORAGEIS REMOVED
RSLV 10/20/2018 10/20/2018 01/08/2022
 
014 (999) OTHER
(ALL FLOORS)NOTE 3: ENTIRE COUNT FOR THE HOTEL AND RESIDENCES FLOOR DESRIPTIONSARE WAY OFF NEED TO BE ADDED TO NEW APP TO BE FILED ALONG WITH ALLOTHER ITEMS ON ALL NOTES
RSLV 10/20/2018 10/20/2018 01/08/2022
 
015 (999) OTHER
(ALL FLOORS)NOTE 2: GENERATOR AND RELATED WIRING AND EQUIPMENT NOT ONAPPLICATION OR DRAWINGS NOT INSPECTED
RSLV 10/20/2018 10/20/2018 08/21/2021
 
016 (999) OTHER
(ALL FLOORS)NOTE 1: ALL MOTORS ARE NOT ON APPLICATION (MOTORS, PUMPS, CHILLERS,HVAC, AIR UNITS , BOILERS , HEATERS, ETC, OF TYPE
RSLV 10/20/2018 10/20/2018 01/08/2022
 
017 ( 31) MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX
(PENTHOUSE)314.16 PENTHOUSE OF HOTEL IN ROUND TURRET ROOMS ON ROOF BOXES INMILL WORK OUTLETS (BOX FILL IS OVER FILED BOXES UNDERSIZED
RSLV 10/20/2018 10/20/2018 01/08/2022
 
018 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ROOF)110.2(A) DEFECTIVE SWITCHES IN USE FOR HIGH RISE ELEV. 4 AND 5COOULD NOT OPEN FOR MAIN LINE INSPECTION LINE SIDE
RSLV 10/20/2018 10/20/2018 01/08/2022
 
019 (186) 125V, 15/20AMP RECEPTICAL IN MACHINE AREA NOT GFCI
(ROOF) 620.85 NOT ALL RECEPTACLES GFCI PROTECTED
RSLV 10/20/2018 10/20/2018 01/08/2022
 
020 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)110.2(B) INSTALLATION DOENT MATCH THE ADVISORY DRAWINGS (COPPERDETAIL THRU AND SECTION, ALL FEEDERS NOT AS PER DRAWING CU INSTALLEDIS AL, LAY OUT DOESN'T MATCH DRAWING AND NO DRAWING FOR THEGENERATOR AND ATS SWITCHES
RSLV 10/20/2018 10/20/2018 01/08/2022
 
021 (999) OTHER
(SUB-CELLAR)110.26 ALL DOORS IN ELECTRICAL ROOMS WITH A RATING OF 1200AMPS ORMORE MUST HAVE PANIC HARDWARE
RSLV 10/20/2018 10/20/2018 08/21/2021
 
022 (999) OTHER
(SUB-CELLAR)110.21, 22 ALL SERVICE SWITCHES ARE NOT IDENTIFIED PROPERLY WITHDURABLE MEANS
RSLV 10/20/2018 10/20/2018 08/21/2021
 
023 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 011)AM 408.60.C NOT PROVIDED WARNING LABEL 277V. 480V . GENERATOREQUIPMENT
RSLV 08/21/2021 08/21/2021 01/08/2022
 
024 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011)AM 110.2.B IMPROPER MANUFACTURE CIRCUIT BREAKER AT LOAD BANKGENERATOR .
RSLV 08/21/2021 08/21/2021 01/08/2022
 
025 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(FLOOR: 011)AM 110.2.B IMPROPER SIDE OF CONDUCTORS . LINE SIDE PANEL EMDB 1EMDB 2
RSLV 08/21/2021 08/21/2021 01/08/2022
 
026 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 052)250.148 CONTINUITY AND ATTACHMENT OF EGC TO ENCLOSURE . FIRE PUMPROOM SPLICE BOX 18 X 18 IN . JOCKEY PUMP TAP
RSLV 08/21/2021 08/21/2021 01/08/2022
 
027 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(FLOOR: 052)110.14 IMPROPER TERMINATION AT 2 PORT POLARIS CONNECTOR . TWOCONDUCTORS UNDER ONE PORT . SPLICE BOX 18 X 18 IN . WHERE TAPJOCKEY PUMP . FIRE PUMP ROOM.
RSLV 08/21/2021 08/21/2021 01/08/2022
 
028 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS)AM 700.9 NOT PROVIDED PERMANENTLY AFFIXED IDENTIFICATION NAMEPLATEYELLOW IN COLOR WITH BLACK LETTERING AT EMERGENCY CKTS. ALLACCESSIBLE RACEWAYS . BOXES . ENCLOSURES. ATS GENERATORS.
RSLV 08/21/2021 08/21/2021 01/08/2022
 
029 (212) NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM
(ALL FLOORS)250.30 SUBCELLAR T SC 1 225 XMFR. CELLAR 30 KVA XFMR . CELLAR 75KVA XFMR FIRE PUMP XFMR TCFP4. TCFP3. TCFP2. TCFP1
RSLV 08/21/2021 08/21/2021 01/08/2022
 
030 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)AM 110.2.B IMPROPER TYPE FUSE . BUS DUCT DISC SW FLOOR 48. 42.30.20.19
RSLV 08/21/2021 08/21/2021 01/08/2022
 
031 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)AM 110.2.B IMPROPER TYPE FUSE . FIRE ALARM DISC SW GENERATOR..CELLAR TRANS S 800 A DISC SW DP HC 5R. CELLAR TRANS S DP HC FP
RSLV 08/21/2021 08/21/2021 01/08/2022
 
032 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)AM 110.2.B IMPROPER SIZE FUSE. FLOOR 11TH FIRE ALARM DISC SWGENERATOR . CELLAR ATS ROOM FIRE ALARM DISC SW. CELLAR SWBD MAIN 5SERVICE SW SDB2. CELLAR 200 A DISC SW PP H1 R11
RSLV 08/21/2021 08/21/2021 01/08/2022
 
033 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)AM 110.2.B DO NOT FIND MI CABLE AT FIRE PUMP .FLOOR 52TH . FLOOR32TH TWO PUMP. CELLAR MI CABLE FIRE PUMP ROOM. 145 KVA XFMR TCFP1
RSLV 08/21/2021 08/21/2021 01/08/2022
 
034 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)AM 110.2.B IMPROPER SIZE CONDUCTOR . FIRE PUMP . FROM CONTROL BOX TOMOTOR. FIRE PUMP FLOOR 52TH. FIRE PUMP FLOOR 32 TWO PUMP. CELLARFIRE PUMP FROM CONTROL BOX TO MOTOR
RSLV 08/21/2021 08/21/2021 01/08/2022
 
035 (281) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(ALL FLOORS)250.64.E EGC NOT CONTINUOUS . SUBCELLAR T SC 1 225 KVA XFMR ATCOLLECTOR BAR . FLOOR 11TH GEC AT GENERATOR
RSLV 08/21/2021 08/21/2021 01/08/2022
 
036 (308) CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED
(ALL FLOORS)110.14 DOUBLE LUGGING . BUS DUCT DISC SW FLOOR 42. 30. 19. FLOOR 32TH JOCKEY PUMP DISC SW TWO UNITS . CELLAR ATS ROOM ASCO 300 SERIES4 POLE. CELLAR JOCKEY PUMP
RSLV 08/21/2021 08/21/2021 01/08/2022
 
037 (138) METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY
(CELLAR)300.10 MIGB COME OFF . 4 IN RMC BOTTOM OF 2000A SDB 1 METER BANK
RSLV 08/21/2021 08/21/2021 01/08/2022
 
038 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(CELLAR) AM 760.41.D FIRE ALARM MISSING LABELED
RSLV 08/21/2021 08/21/2021 01/08/2022
 
039 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR)250.30 AFFIDAVIT LETTER STATING SEPARATELY DERIVED AC SYSTEM IN GND. XFMR TC1 . TC2. TC3.TC4 AND WIRING IS INSTALLED ACCORDING TO THECURRENT CODE
RSLV 08/21/2021 08/21/2021 01/08/2022
 
040 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM 110.2.B SWBD DP C 1 SIZE OF CIRCUIT BREAKER AMPERE IMPROPER
RSLV 08/21/2021 08/21/2021 01/08/2022
 
041 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) AM 110.2.B ONE LINE DIAGRAM METER BANK MB C2 NEED UPDATE
RSLV 08/21/2021 08/21/2021 01/08/2022
 
042 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM 110.2.B LAY OUT DRAWING NEED UPDATE . METER BANK MC C1 . MC C2
RSLV 08/21/2021 08/21/2021 01/08/2022
 
043 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM 110.2.B 150 KVA XFMR FIRE PUMP NEEDS UPDATE LOCATION. NEWLOCATION FIRE PUMP
RSLV 08/21/2021 08/21/2021 01/08/2022
 
044 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR)AM 110.2.B AM 230.42.A IMPROPER NUMBER OF BUSBAR DENSITY . SWBDSDB1 T OUT
RSLV 08/21/2021 08/21/2021 01/08/2022
 
045 (281) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(CELLAR) 260.64.C GEC NOT CONTINUES SERVICE SW FIRE ALARM
RSLV 08/21/2021 08/21/2021 01/08/2022
 
046 ( 42) BUSHINGS ARE MISSING OR LOOSE
(CELLAR) 300.4.G INSULATED FITTING LOOSE . TRANS S DP HC 5R
RSLV 08/21/2021 08/21/2021 01/08/2022
 
047 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) 250.24.A FIRE PUMP SERVICE SW
RSLV 08/21/2021 08/21/2021 01/08/2022
 
048 (999) OTHER
(CELLAR)PAA REQUIRED . REMOVE 1 SERVICE SW UP TO 100 A FOR A TOTAL OF ONE.ADD 2 SERVICE SW OVER 1200A FOR A TOTAL OF 8. ADD 2 SERVICE SW UPTO 1200A FOR A TOTAL OF 5
RSLV 08/21/2021 08/21/2021 01/08/2022
 
049 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(SUB-CELLAR)250.50 ALL GROUNDING ELECTRODES SHALL BE BONDED TOGETHER
RSLV 08/21/2021 08/21/2021 01/08/2022
 
050 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(SUB-CELLAR)AM 110.2.B ONE LINE DRAWING NEED UPDATE . MISSING 400 A ATS RELATEDWITH 225 KVA TRANSFORMER AND 400A DISTRIBUTION PANEL
RSLV 08/21/2021 08/21/2021 01/08/2022
 
051 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(ALL FLOORS) EMDB-1 AND EMDB-2 FEED FROM GENERATOR CONDUCTORS ON ONE LINE NOT AS PER DRAWING (PRINT SHOWS) EMDB-1 SHOWS 2 SETS OFF 4 WIRE 600 MCM AND EMDB-2 SHOWS 4 SETS OF 4 WIRE 350 MCM. /WHAT IS INSTALLED EMDB- 1 IS 3 SETS OF 4 WIRE 750 MCM AL. AND EMDB-2 IS 4 SETS OF 4 WIRE OF 500 AL. AND FIRE ALARM SWITCH ON GENERATOR FUSES NOT AS
RSLV 01/08/2022 01/08/2022 02/05/2022
 
052 (999) OTHER
(ALL FLOORS)ALL FLOOR INSUFFICIENT COUNT FOR FIXTURES , MOTORS ,RECEPTACLES,ETC.
RSLV 01/08/2022 01/08/2022 02/05/2022