| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS)408.4 PANELS IN ALL AREAS DO NOT HAVE DIRECTORIES (THRU OUTINFRASTRUCTURE , HOTEL AND RESIDENCE ) |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS)210.12(B) CAFCI BREAKERS MISSING IN ALL CONDOS NEED DIRECTORIES TOSHOW ACCURATE MISSING CBS (SEE ALL LISTED IN CODE SECTION ) |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 003 |
( 9) |
SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY (ALL FLOORS)430.75 NO ACCESS OR NO DISCONNECT PROVIDED FOR ALL UNITS MOUNTED INCEILINGS OF THE CONDOS NEED RATING FOR SPEC FOR BREAKER SIZING |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)406.8(B) ALL OUTDOOR GFCI NEED WR TYPE AND IN USE COVERS ROOF TO THEBOTTOM |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)BEFORE SCHEDULING ANOTHER APPOINTMETN CONTACT TUR IN MANHATTANOFFICE TO GO OVER THE APPLICATIONS SUBMITTED AND AMENDED |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS)NOTE 6 RESTAURANT NOT INSPECTED WINDOW FOR INSPECTION BETWEEN 3 AND5 |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS)314.20 OUTLETS SET BACK IN HITCHEN AREA BACKSPLASHES AND RELATEDSTONE (ALSO SEE BATHROOMS MORE THAN CODE ALLOWED 1/4" CHECK ALLOUTLETS FOR BONDING |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS) DISCONNECT NOT PROVIDED FOR STEAM GENERATOR ALL CONDOS |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)332. MI CABLE NOT INSTALLED AS PER CODE ARTICLE THRU OUT |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)NOTE 5: MUST GET A FULL COUNT OF PANELS, FEEDERS, SERVICE FEEDERS,TRANSFORMERS , ETC AND ADD MISSING TO THE NEW APP. |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)314.20 OUTLETS IN ALL MILL AND BASE MOLDING (GYMS, HOTEL ROOMS,HALLS, LOBBY AREAS IN STONE THRU OUT SET BACK MORE THAN 3INCHES INSOME AREAS EXTENSION COLLAR AND SLEEVE NEED GYM AREAS ALL BASE INHOTEL ROOMS NEED FULL ADAPTER FOR 2INCHES |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 012 |
(999) |
OTHER (ALL FLOORS)NOTE 4: DURING INSPECTION ONLY INSPECTED 4 CONDOS NO ACCESS TOOTHERS AT TIME OF INSPECTION ONLY INSPECTED 5 HOTEL ROOMS MOTE TO BEINSPECTED IN BOTH AREAS , DID NOT INSPECT RESTAURANTS AND RELATEDAREAS |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS)110.26 ALL ELECTRICAL ROOMS TRU OUT TO BE INSPEECTED WHEN STORAGEIS REMOVED |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 014 |
(999) |
OTHER (ALL FLOORS)NOTE 3: ENTIRE COUNT FOR THE HOTEL AND RESIDENCES FLOOR DESRIPTIONSARE WAY OFF NEED TO BE ADDED TO NEW APP TO BE FILED ALONG WITH ALLOTHER ITEMS ON ALL NOTES |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 015 |
(999) |
OTHER (ALL FLOORS)NOTE 2: GENERATOR AND RELATED WIRING AND EQUIPMENT NOT ONAPPLICATION OR DRAWINGS NOT INSPECTED |
RSLV |
10/20/2018 |
10/20/2018 |
08/21/2021 |
| |
| 016 |
(999) |
OTHER (ALL FLOORS)NOTE 1: ALL MOTORS ARE NOT ON APPLICATION (MOTORS, PUMPS, CHILLERS,HVAC, AIR UNITS , BOILERS , HEATERS, ETC, OF TYPE |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 017 |
( 31) |
MORE THAN ALLOWABLE # OF CONDUCTORS ARE IN OUTLET BOX (PENTHOUSE)314.16 PENTHOUSE OF HOTEL IN ROUND TURRET ROOMS ON ROOF BOXES INMILL WORK OUTLETS (BOX FILL IS OVER FILED BOXES UNDERSIZED |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 018 |
( 17) |
DEFECTIVE SWITCHES ARE IN USE (ROOF)110.2(A) DEFECTIVE SWITCHES IN USE FOR HIGH RISE ELEV. 4 AND 5COOULD NOT OPEN FOR MAIN LINE INSPECTION LINE SIDE |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 019 |
(186) |
125V, 15/20AMP RECEPTICAL IN MACHINE AREA NOT GFCI (ROOF) 620.85 NOT ALL RECEPTACLES GFCI PROTECTED |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 020 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)110.2(B) INSTALLATION DOENT MATCH THE ADVISORY DRAWINGS (COPPERDETAIL THRU AND SECTION, ALL FEEDERS NOT AS PER DRAWING CU INSTALLEDIS AL, LAY OUT DOESN'T MATCH DRAWING AND NO DRAWING FOR THEGENERATOR AND ATS SWITCHES |
RSLV |
10/20/2018 |
10/20/2018 |
01/08/2022 |
| |
| 021 |
(999) |
OTHER (SUB-CELLAR)110.26 ALL DOORS IN ELECTRICAL ROOMS WITH A RATING OF 1200AMPS ORMORE MUST HAVE PANIC HARDWARE |
RSLV |
10/20/2018 |
10/20/2018 |
08/21/2021 |
| |
| 022 |
(999) |
OTHER (SUB-CELLAR)110.21, 22 ALL SERVICE SWITCHES ARE NOT IDENTIFIED PROPERLY WITHDURABLE MEANS |
RSLV |
10/20/2018 |
10/20/2018 |
08/21/2021 |
| |
| 023 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (FLOOR: 011)AM 408.60.C NOT PROVIDED WARNING LABEL 277V. 480V . GENERATOREQUIPMENT |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 024 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011)AM 110.2.B IMPROPER MANUFACTURE CIRCUIT BREAKER AT LOAD BANKGENERATOR . |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 025 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (FLOOR: 011)AM 110.2.B IMPROPER SIDE OF CONDUCTORS . LINE SIDE PANEL EMDB 1EMDB 2 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 026 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (FLOOR: 052)250.148 CONTINUITY AND ATTACHMENT OF EGC TO ENCLOSURE . FIRE PUMPROOM SPLICE BOX 18 X 18 IN . JOCKEY PUMP TAP |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 027 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED (FLOOR: 052)110.14 IMPROPER TERMINATION AT 2 PORT POLARIS CONNECTOR . TWOCONDUCTORS UNDER ONE PORT . SPLICE BOX 18 X 18 IN . WHERE TAPJOCKEY PUMP . FIRE PUMP ROOM. |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 028 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS)AM 700.9 NOT PROVIDED PERMANENTLY AFFIXED IDENTIFICATION NAMEPLATEYELLOW IN COLOR WITH BLACK LETTERING AT EMERGENCY CKTS. ALLACCESSIBLE RACEWAYS . BOXES . ENCLOSURES. ATS GENERATORS. |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 029 |
(212) |
NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM (ALL FLOORS)250.30 SUBCELLAR T SC 1 225 XMFR. CELLAR 30 KVA XFMR . CELLAR 75KVA XFMR FIRE PUMP XFMR TCFP4. TCFP3. TCFP2. TCFP1 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 030 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM 110.2.B IMPROPER TYPE FUSE . BUS DUCT DISC SW FLOOR 48. 42.30.20.19 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 031 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM 110.2.B IMPROPER TYPE FUSE . FIRE ALARM DISC SW GENERATOR..CELLAR TRANS S 800 A DISC SW DP HC 5R. CELLAR TRANS S DP HC FP |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 032 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM 110.2.B IMPROPER SIZE FUSE. FLOOR 11TH FIRE ALARM DISC SWGENERATOR . CELLAR ATS ROOM FIRE ALARM DISC SW. CELLAR SWBD MAIN 5SERVICE SW SDB2. CELLAR 200 A DISC SW PP H1 R11 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 033 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM 110.2.B DO NOT FIND MI CABLE AT FIRE PUMP .FLOOR 52TH . FLOOR32TH TWO PUMP. CELLAR MI CABLE FIRE PUMP ROOM. 145 KVA XFMR TCFP1 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 034 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)AM 110.2.B IMPROPER SIZE CONDUCTOR . FIRE PUMP . FROM CONTROL BOX TOMOTOR. FIRE PUMP FLOOR 52TH. FIRE PUMP FLOOR 32 TWO PUMP. CELLARFIRE PUMP FROM CONTROL BOX TO MOTOR |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 035 |
(281) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (ALL FLOORS)250.64.E EGC NOT CONTINUOUS . SUBCELLAR T SC 1 225 KVA XFMR ATCOLLECTOR BAR . FLOOR 11TH GEC AT GENERATOR |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 036 |
(308) |
CONDUCTORS ARE NOT PROPERLY INSTALLED/TERMINATED (ALL FLOORS)110.14 DOUBLE LUGGING . BUS DUCT DISC SW FLOOR 42. 30. 19. FLOOR 32TH JOCKEY PUMP DISC SW TWO UNITS . CELLAR ATS ROOM ASCO 300 SERIES4 POLE. CELLAR JOCKEY PUMP |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 037 |
(138) |
METAL RACEWAYS AND ENCLOSURES DO NOT HAVE ELECTRICAL CONTINUITY (CELLAR)300.10 MIGB COME OFF . 4 IN RMC BOTTOM OF 2000A SDB 1 METER BANK |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 038 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (CELLAR) AM 760.41.D FIRE ALARM MISSING LABELED |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 039 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (CELLAR)250.30 AFFIDAVIT LETTER STATING SEPARATELY DERIVED AC SYSTEM IN GND. XFMR TC1 . TC2. TC3.TC4 AND WIRING IS INSTALLED ACCORDING TO THECURRENT CODE |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 040 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AM 110.2.B SWBD DP C 1 SIZE OF CIRCUIT BREAKER AMPERE IMPROPER |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 041 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR) AM 110.2.B ONE LINE DIAGRAM METER BANK MB C2 NEED UPDATE |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 042 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AM 110.2.B LAY OUT DRAWING NEED UPDATE . METER BANK MC C1 . MC C2 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 043 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AM 110.2.B 150 KVA XFMR FIRE PUMP NEEDS UPDATE LOCATION. NEWLOCATION FIRE PUMP |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 044 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (CELLAR)AM 110.2.B AM 230.42.A IMPROPER NUMBER OF BUSBAR DENSITY . SWBDSDB1 T OUT |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 045 |
(281) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (CELLAR) 260.64.C GEC NOT CONTINUES SERVICE SW FIRE ALARM |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 046 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (CELLAR) 300.4.G INSULATED FITTING LOOSE . TRANS S DP HC 5R |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 047 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (CELLAR) 250.24.A FIRE PUMP SERVICE SW |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 048 |
(999) |
OTHER (CELLAR)PAA REQUIRED . REMOVE 1 SERVICE SW UP TO 100 A FOR A TOTAL OF ONE.ADD 2 SERVICE SW OVER 1200A FOR A TOTAL OF 8. ADD 2 SERVICE SW UPTO 1200A FOR A TOTAL OF 5 |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 049 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (SUB-CELLAR)250.50 ALL GROUNDING ELECTRODES SHALL BE BONDED TOGETHER |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 050 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (SUB-CELLAR)AM 110.2.B ONE LINE DRAWING NEED UPDATE . MISSING 400 A ATS RELATEDWITH 225 KVA TRANSFORMER AND 400A DISTRIBUTION PANEL |
RSLV |
08/21/2021 |
08/21/2021 |
01/08/2022 |
| |
| 051 |
(176) |
INSTALLATION DOES NOT MEET CODE REQUIREMENTS (ALL FLOORS) EMDB-1 AND EMDB-2 FEED FROM GENERATOR CONDUCTORS ON ONE LINE NOT AS PER DRAWING (PRINT SHOWS) EMDB-1 SHOWS 2 SETS OFF 4 WIRE 600 MCM AND EMDB-2 SHOWS 4 SETS OF 4 WIRE 350 MCM. /WHAT IS INSTALLED EMDB- 1 IS 3 SETS OF 4 WIRE 750 MCM AL. AND EMDB-2 IS 4 SETS OF 4 WIRE OF 500 AL. AND FIRE ALARM SWITCH ON GENERATOR FUSES NOT AS |
RSLV |
01/08/2022 |
01/08/2022 |
02/05/2022 |
| |
| 052 |
(999) |
OTHER (ALL FLOORS)ALL FLOOR INSUFFICIENT COUNT FOR FIXTURES , MOTORS ,RECEPTACLES,ETC. |
RSLV |
01/08/2022 |
01/08/2022 |
02/05/2022 |