Electrical Application Details for App #: M395773
Premises: 413 EAST 52 STREET MANHATTAN BIN: 1078257     Block: 1364   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 415 E 52 ST Census Tract:   86.03 Health Area:  5000
10BA Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10022 Community Board:   106
DOB Cross Street(s):    1 AVENUE,    DEAD END
Status:   C - JOB IS SIGNED OFF 12/10/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/08/2017 12:25 PM
Application Entered:   05/08/2017 Job Start Date:   05/09/2017
Last Change:   12/10/2019 Job End Date:   05/09/2018
Appointment Status:   
Last Inspection By:   RIVERA, F       On     12/10/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011693 Licensee Name: EVANGELINA APRILAKIS
Firm: 004165 Firm Name: EUROPA ELECTRIC OF NY COR
Firm Phone: 718-661-2660  Firm Address: 18-41 STEINWAY STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $91.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DENNIS EULAU
Owner Business Name: NA
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  30 CKTS 70 AMP
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
010  10BA  10  32    14  10             
Buildings Total 10  32    14  10                
Total Units : 66 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 09/18/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395773
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/05/2018 02/06/2018 JRP V (45) (3)
INSPECTION COMMENTS: FAIL
 
(2) 02/13/2018 02/14/2018 AYC J Y (64) (1)
INSPECTION COMMENTS: FAIL
 
(3) 03/16/2018 03/16/2018 TUR N (40) (0) Y
INSPECTION COMMENTS: ELECTRICIAN PRESENT BUT NO ACCESS, NOTE: TO INSPECTOR CONTRACTOR IS GOING TO ADD QUAD AND TWIN BREAKERS MAKE SURE PANEL IS LISTED FOR THESE TYPE BREAKERS AND THAT THEY STILL HAVE RESTRICTIONS, QUADS COME ONLY WITH RESTRICTIONS <DIRECTORY ?
 
(4) 09/04/2018 09/04/2018 BMP N (10) (0) Y
INSPECTION COMMENTS: OCCUPANT UNABLE TO SUPPORT INSPECTION. NO ACCESS.
 
(5) 09/17/2018 09/18/2018 BMP J X (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR ARRIVED LATE. HE SAID HE WOULD RESCHEDULE. JOB IN PROGRESS.
 
(6) 02/01/2019 02/01/2019 AYC J Y (39) (0)
INSPECTION COMMENTS: FAIL. LOAD CALCULATION STILL NEEDS TO BE PROVIDED.
 
(7) 12/10/2019 12/10/2019 FRI C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-19-000028881

OBJECTION FOR APPLICATION #: M395773
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 010) NEEDS GROUPING AND HANDLE TIES 210.4
RSLV 02/05/2018 02/05/2018 02/01/2019
 
002 (999) OTHER
(FLOOR: 010)BATHROOM GFCI CIRCUIT SHARING WITH BEDROOM RECEPTACLE 210.11(C)(3)
RSLV 02/05/2018 02/05/2018 02/13/2018
 
003 (999) OTHER
(FLOOR: 010)THERE IS A SHORT IN THE GENERAL LIGHTING CIRCUIT 110.3,110.7
RSLV 02/05/2018 02/05/2018 02/13/2018
 
004 (999) OTHER
(FLOOR: 010)LOAD LETTER NEEDED FOR NEW BRANCH CIRCUITS ON THE EXISTING FEEDERS.ART. 220.40
RSLV 02/13/2018 02/13/2018 12/10/2019