NYC Department of Buildings
Electrical Application Details for App #: M395577
Premises: 239 ELIZABETH STREET MANHATTAN BIN: 1007906     Block: 508   Lot: 42
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 239 ELIZABETH ST Census Tract:   43 Health Area:  6800
APT # 2, 4, 5 Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    EAST HOUSTON STREET
Status:   C - JOB IS SIGNED OFF 02/15/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/03/2017 12:57 PM
Application Entered:   05/03/2017 Job Start Date:   05/03/2017
Last Change:   02/15/2018 Job End Date:   03/03/2018
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     02/13/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010990 Licensee Name: DIMOS PAPADIMAS
Firm: 002332 Firm Name: VERTEX ELECTRIC CORP.
Firm Phone: 718-997-9090  Firm Address: 28-41 STEINWAY STREET ASTORIA NY 11103 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $291.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TERRENCE LOWENBERG
Owner Business Name: 477 AMSTERDAM REALTY, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  #3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  20 CIRCUITS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  #2  30  44  10  30             
002  30  26  12  30         
004  #4  30  44  10  30             
004  30  26  12  30         
005  #5  30  44  10  30             
005  30  26  12  30         
Buildings Total 180  210  12  66  180              
Total Units : 654 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/26/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  EXISTING SERVICE REMAIN. P/I SUB C/B PANELS, SUB-FEEDERS, OUTLETS, SWITCHES, A/C OUTLETS, GFI OUTLETS, SMOKE DETECTORS, LIGHTING FIXTURES.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395577
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/25/2018 01/26/2018 TUR V (70) (17)
INSPECTION COMMENTS: OBJECTIONS ISSUED , APPLY OBJECTIONS TO ALL THREE APTS AND SERVICE RISERS SEE OBJECTIONS FOR DETAILS
 
(2) 02/13/2018 02/13/2018 CBK C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED. ONLY INSPECT 3 APMTS. 2, 4 AND 5.

OBJECTION FOR APPLICATION #: M395577
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(FLOOR: 005)320.40 SEE IN PANELS KOS FOR THE ARMORED CABLE CONNECTORS OVERSIZED NEED DOUGHNUTS (WASHERS )
RSLV 01/25/2018 01/25/2018 02/13/2018
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 005)408.4 ALL DIRECTORIES ARE NOT COMPLETE AND ACCURATE ALL FLOORS
RSLV 01/25/2018 01/25/2018 02/13/2018
 
003 ( 52) TEMPORARY OPEN WIRING FEEDS OTHER FLOORS
(FLOOR: 005)210.8 KITCHEN RECEPTACLES ON WALL 6FT FROM SINK (OPPOSITE WALL) MUSTHAVE GFCI PROTECTION
RSLV 01/25/2018 01/25/2018 02/13/2018
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 005)210.12(B) NOT ALL CIRCUITS REQUIRED ARE AFCI PROTECTED SEE ROOMSLISTED , HALLS, CLOSETS SIMILAR ROOMS 110VOLT OUT IN LAUNDRY CLOSETAND TYPICAL
RSLV 01/25/2018 01/25/2018 02/13/2018
 
005 (999) OTHER
(FLOOR: 005)314.20 OUTLETS SET BACK IN KITCHEN BACK SPLASH ALL FLOORS
RSLV 01/25/2018 01/25/2018 02/13/2018
 
006 (235) MAIN BREAKER NOT BOLTED IN
(BASEMENT)408.36(D) BREAKER FOR THE APT PANELS NOT SECURED IN THE METER BANKENCLOSURES THEY ARE FLOATING AND NOT PROPERLY SNAPPED IN (MUST FIXASAP)
RSLV 01/25/2018 01/25/2018 02/13/2018
 
007 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT)358.30 EMT IS NOT PROPERLY SUPPORTED SEE SECTION WHERE CONDUIT TIESTO BASEMENT PULL BOX
RSLV 01/25/2018 01/25/2018 02/13/2018
 
008 (999) OTHER
(BASEMENT)110.2, 3 PROVIDE MANUFACTURERS SPECIFICATION FOR METER BANK FORRATINGS ALLOWED
RSLV 01/25/2018 01/25/2018 02/13/2018
 
009 (999) OTHER
(BASEMENT)NOTE 1: WORK IS FOR THREE APARTMENTS ONLY OTHER APARTMENTS THRU OUTNOT ON THIS APPLICATION
RSLV 01/25/2018 01/25/2018 02/13/2018
 
010 (999) OTHER
(BASEMENT)110.2 PULL BOXES FOR RISERS ON THE EXTERIOR OF THE BUILDING ARE NOTOUTDOOR RATED INDOOR PULL BOXES 10X10 IN USE THROUGH OUT
RSLV 01/25/2018 01/25/2018 02/13/2018
 
011 (999) OTHER
(BASEMENT)110.2 DAMGED INSULATION FOR PANEL RISERS SEE IN METER BANK AND PULLPOINTS
RSLV 01/25/2018 01/25/2018 02/13/2018
 
012 (999) OTHER
(BASEMENT)110.21,22 ALL EQUIPMENT MUST BE LABELED WITH DURABLE MEANS NOT FADEDMARKER (LABELS )
RSLV 01/25/2018 01/25/2018 02/13/2018
 
013 (999) OTHER
(BASEMENT)250.92 SERVICE EQUIPMENT , CONDUITS , AND PULL BOXES NOT BONDEDPROPERLY SEE BROKEN KO IN BASEMENT PULL BOX 1.5 INCH CONDUIT IS INTHE PULL BOX (COLLAPSED KO ) ALSO MUST TIGHTEN ALL CONNECTIONS BYMETER BANK
RSLV 01/25/2018 01/25/2018 02/13/2018
 
014 (999) OTHER
(BASEMENT) 110.12 KO SEALS OPEN FROM SERVICE TO PANELS
RSLV 01/25/2018 01/25/2018 02/13/2018
 
015 (999) OTHER
(BASEMENT)410.11 ALL PENETRATIONS IN EXTERIOR WALLS MUST BE SEALED WITHAPPROVED MATERIALS FROM BASEMENT TO 5TH FLOOR ALL PENETRATIONS
RSLV 01/25/2018 01/25/2018 02/13/2018
 
016 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ROOF)240.3 OCP FOR THE 3 HVAC UNITS ON ROOF OVER FUSED MANUFACTURERS SPECCALLS FOR MOP 15 AMP BREAKER OR FUSE (CURRENTLY 20AMP BREAKER ANDAT DISCONNECT 30AMP FUSES)
RSLV 01/25/2018 01/25/2018 02/13/2018
 
017 (307) NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT
(ROOF) 210.63 NO GFCI WITHIN 25FT OF HVAC UNIT FOR SERVICE
RSLV 01/25/2018 01/25/2018 02/13/2018