| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
#3 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
20 CIRCUITS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (FLOOR: 005)320.40 SEE IN PANELS KOS FOR THE ARMORED CABLE CONNECTORS OVERSIZED NEED DOUGHNUTS (WASHERS ) |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 002 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 005)408.4 ALL DIRECTORIES ARE NOT COMPLETE AND ACCURATE ALL FLOORS |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 003 |
( 52) |
TEMPORARY OPEN WIRING FEEDS OTHER FLOORS (FLOOR: 005)210.8 KITCHEN RECEPTACLES ON WALL 6FT FROM SINK (OPPOSITE WALL) MUSTHAVE GFCI PROTECTION |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 004 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 005)210.12(B) NOT ALL CIRCUITS REQUIRED ARE AFCI PROTECTED SEE ROOMSLISTED , HALLS, CLOSETS SIMILAR ROOMS 110VOLT OUT IN LAUNDRY CLOSETAND TYPICAL |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 005 |
(999) |
OTHER (FLOOR: 005)314.20 OUTLETS SET BACK IN KITCHEN BACK SPLASH ALL FLOORS |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 006 |
(235) |
MAIN BREAKER NOT BOLTED IN (BASEMENT)408.36(D) BREAKER FOR THE APT PANELS NOT SECURED IN THE METER BANKENCLOSURES THEY ARE FLOATING AND NOT PROPERLY SNAPPED IN (MUST FIXASAP) |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 007 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (BASEMENT)358.30 EMT IS NOT PROPERLY SUPPORTED SEE SECTION WHERE CONDUIT TIESTO BASEMENT PULL BOX |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 008 |
(999) |
OTHER (BASEMENT)110.2, 3 PROVIDE MANUFACTURERS SPECIFICATION FOR METER BANK FORRATINGS ALLOWED |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 009 |
(999) |
OTHER (BASEMENT)NOTE 1: WORK IS FOR THREE APARTMENTS ONLY OTHER APARTMENTS THRU OUTNOT ON THIS APPLICATION |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 010 |
(999) |
OTHER (BASEMENT)110.2 PULL BOXES FOR RISERS ON THE EXTERIOR OF THE BUILDING ARE NOTOUTDOOR RATED INDOOR PULL BOXES 10X10 IN USE THROUGH OUT |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 011 |
(999) |
OTHER (BASEMENT)110.2 DAMGED INSULATION FOR PANEL RISERS SEE IN METER BANK AND PULLPOINTS |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 012 |
(999) |
OTHER (BASEMENT)110.21,22 ALL EQUIPMENT MUST BE LABELED WITH DURABLE MEANS NOT FADEDMARKER (LABELS ) |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 013 |
(999) |
OTHER (BASEMENT)250.92 SERVICE EQUIPMENT , CONDUITS , AND PULL BOXES NOT BONDEDPROPERLY SEE BROKEN KO IN BASEMENT PULL BOX 1.5 INCH CONDUIT IS INTHE PULL BOX (COLLAPSED KO ) ALSO MUST TIGHTEN ALL CONNECTIONS BYMETER BANK |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 014 |
(999) |
OTHER (BASEMENT) 110.12 KO SEALS OPEN FROM SERVICE TO PANELS |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 015 |
(999) |
OTHER (BASEMENT)410.11 ALL PENETRATIONS IN EXTERIOR WALLS MUST BE SEALED WITHAPPROVED MATERIALS FROM BASEMENT TO 5TH FLOOR ALL PENETRATIONS |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 016 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ROOF)240.3 OCP FOR THE 3 HVAC UNITS ON ROOF OVER FUSED MANUFACTURERS SPECCALLS FOR MOP 15 AMP BREAKER OR FUSE (CURRENTLY 20AMP BREAKER ANDAT DISCONNECT 30AMP FUSES) |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |
| |
| 017 |
(307) |
NO RECEPTACLE OUTLET WITHIN 25 FEET FOR HVAC EQUIPMENT (ROOF) 210.63 NO GFCI WITHIN 25FT OF HVAC UNIT FOR SERVICE |
RSLV |
01/25/2018 |
01/25/2018 |
02/13/2018 |