BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M395541
Premises: 25 COOPER SQUARE MANHATTAN BIN: 1087921     Block: 461   Lot: 3
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 25 COOPER SQ Census Tract:   38 Health Area:  6500
1ST FLOOR RESTAURANT Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10003 Community Board:   103
Related Job Number:    123059910
DOB Cross Street(s):   EAST 5 STREET,    EAST 6 STREET
Status:   C - JOB IS SIGNED OFF 07/25/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/03/2017 7:52 AM
Application Entered:   05/03/2017 Job Start Date:   05/03/2017
Last Change:   07/25/2017 Job End Date:   06/30/2017
Appointment Status:   
Last Inspection By:   CAMPBELL, C       On     07/25/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011008 Licensee Name: LAURENCE H ROBIN
Firm: 001260 Firm Name: ROBIN ELECTRICAL CO., INC
Firm Phone: 718-292-6535  Firm Address: 437 EAST 165TH ST. B704 BRONX NY 10456 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
T - TEMPORARY LIGHT & POWER
Total Fee:  $123.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALEX BERTMAN
Owner Business Name: STANDARD INTERNATIONAL
Authorized Representative:  BENI MITAJ
Relationship To Owner:   G C


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  TO PANEL AT FRONT OF REST
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100 AMP FEEDER
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND  REST  25  17      25  15         
Buildings Total 25  17      25     15           
Total Units : 82 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/11/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ADDING A PANEL FOR HEATERS, MOVING LIGHTING AROUND.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395541
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/10/2017 07/11/2017 CBK V (45) (4)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 07/25/2017 07/25/2017 CLC C R (43) (0)
INSPECTION COMMENTS: INSPECTION PASS

OBJECTION FOR APPLICATION #: M395541
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (111) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(FLOOR: 001) DOORS FOR HEATERS DOES NOT OPEN PROPERLY.
RSLV 07/10/2017 07/10/2017 07/25/2017
 
002 ( 29) OUTLET BOXES ARE NOT COVERED
(FLOOR: 001) RECEPTACLE MISSING COVER UNDER PANEL.
RSLV 07/10/2017 07/10/2017 07/25/2017
 
003 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 001) DOUBLE POLE BREAKERS USED FOR 110V HEATERS.
RSLV 07/10/2017 07/10/2017 07/25/2017
 
004 (999) OTHER
(FLOOR: 001) BREAKER TIES NEEDED ON SHARED NEUTRAL. 210.4
RSLV 07/10/2017 07/10/2017 07/25/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back