BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M395267
Premises: 123 BANK STREET MANHATTAN BIN: 1011947     Block: 635   Lot: 42
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 123 BANK ST Census Tract:   79 Health Area:  6100
LOBBY Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
Special Place Name:   LOBBY
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 12/26/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/27/2017 10:59 AM
Application Entered:   04/27/2017 Job Start Date:   04/27/2017
Last Change:   12/26/2019 Job End Date:   07/30/2017
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     12/26/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012217 Licensee Name: PHILIP MUZIKANT
Firm: 003539 Firm Name: DMMP ELECTRIC CONSTR. INC
Firm Phone: 718-627-1876  Firm Address: 39 BROADWAY SUITE T25 NEW YORK NY 10006 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
011204 MUZIKANT, DAVID 003539 DMMP ELECTRIC CONSTR. INC RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $56.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: ELK INVESTORS
Authorized Representative:  TRICIA PERUGINI
Relationship To Owner:   BUILDING MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
LOB            75             
Buildings Total         75                
Total Units : 75 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 07/25/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M395267
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/25/2019 07/25/2019 PHG V (35) (4)
INSPECTION COMMENTS: CONTRACTOR INSTALLED LIGHTS OUTLETS ON ALL FLOORS IN COMMON HALLWAYS CONTRACTOR TO FIX APP TO REFLECT WORK
 
(2) 12/26/2019 12/26/2019 STP C R (15) (0)
INSPECTION COMMENTS: PASS. NEW APP FILED DOB NOW M00200102.

OBJECTION FOR APPLICATION #: M395267
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) EXITS SIGNS NOT BONDED 250.148
RSLV 07/25/2019 07/25/2019 12/26/2019
 
002 ( 30) OUTLET BOXES ARE NOT SECURED
(ALL FLOORS) EXIT SIGNS WITH BOXES NO BOX SUPPORT PROVIDED 314.1
RSLV 07/25/2019 07/25/2019 12/26/2019
 
003 (999) OTHER
(ALL FLOORS) NO BOX PROVIDED FOR EXIT SIGNS 300.15
RSLV 07/25/2019 07/25/2019 12/26/2019
 
004 (999) OTHER
(ALL FLOORS) APP DOES NOT MATCH INSTALL
RSLV 07/25/2019 07/25/2019 12/26/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.