| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
1 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
1 |
1-4#1/0 |
| C. Over 1/0 to 250 MCM |
1 |
1-4#3/0 |
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (CELLAR) PANELS. |
RSLV |
08/01/2017 |
08/01/2017 |
08/21/2017 |
| |
| 002 |
(999) |
OTHER (CELLAR)112.5 KVA TRANSFORMER NO GROUNDING ELECTRODE CONDUCTOR TO WATER250.66 250.30 |
OPEN |
08/01/2017 |
08/01/2017 |
|
| |
| 003 |
(999) |
OTHER (CELLAR)SERVICE ENTRANCE $ NEUTRAL NOT BONDED PROPERLY 250.28 250.92 |
OPEN |
08/01/2017 |
08/01/2017 |
|
| |
| 004 |
(999) |
OTHER (CELLAR) LB COVERS MISSING 314.25 |
RSLV |
08/01/2017 |
08/01/2017 |
08/29/2019 |
| |
| 005 |
(999) |
OTHER (CELLAR) NO GROUNDING PROVIDED 60 AMP SERVICE SW. 250.64 |
OPEN |
08/01/2017 |
08/01/2017 |
|
| |
| 006 |
(999) |
OTHER (CELLAR) NO WARNING LABEL PROVIDED ALL 480/277 VOLTS 408.60 |
RSLV |
08/01/2017 |
08/01/2017 |
08/21/2017 |
| |
| 007 |
(999) |
OTHER (SUB-CELLAR) BATTERY CABINETS NOT LISTED US 110.2 |
OPEN |
08/01/2017 |
08/01/2017 |
|
| |
| 008 |
(110) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (BASEMENT) NO PUSH BAR PROVIDED DOOR SWINGS WRONG DIRECTION 110.26 |
OPEN |
08/21/2017 |
08/21/2017 |
|
| |
| 009 |
( 19) |
DEFECTIVE WIRING IS IN USE (BASEMENT) XFRM WIRED IMPROPER 110.3 |
OPEN |
08/21/2017 |
08/21/2017 |
|
| |
| 010 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SMALL SERVICE SW NOT ON PRINT |
RSLV |
08/21/2017 |
08/21/2017 |
08/29/2019 |
| |
| 011 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (SUB-CELLAR) BATTERY CABINET RATED FOR 150 AMPS FUSED AT 200 240.4 |
OPEN |
08/21/2017 |
08/21/2017 |
|
| |
| 012 |
(999) |
OTHER (SUB-CELLAR)BREAKERS RUNNING WARM IN SUB BSMT PANEL NEEDS DERATING 310.15 |
OPEN |
08/21/2017 |
08/21/2017 |
|