BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M394567
Premises: 350 BLEECKER STREET MANHATTAN BIN: 1011189     Block: 620   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 350 BLEECKER ST Census Tract:   73 Health Area:  6400
APT 2C Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10014 Community Board:   102
DOB Cross Street(s):   WEST 10 STREET,    CHARLES STREET
Status:   C - JOB IS SIGNED OFF 10/18/2022
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/10/2017 6:34 PM
Application Entered:   04/10/2017 Job Start Date:   04/11/2017
Last Change:   10/18/2022 Job End Date:   05/11/2017
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     10/18/2022      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010554 Licensee Name: EDWARD T LINES
Firm: 000050 Firm Name: ABBEY ELECTRIC INC
Firm Phone: 718-525-4760  Firm Address: 130-40 180TH STREET JAMAICA NY 11434 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $69.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CATHERINE KRABDENSCHMID
Authorized Representative:  PETE GOULAS
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  20 CIRCUIT REPLACEMENT
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2C  18  20    11  18             
Buildings Total 18  20    11  18                
Total Units : 67 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/12/2022
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M394567
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/12/2022 09/12/2022 ASK V (40) (2)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETED. OBJECTION ISSUED.
 
(2) 10/18/2022 10/18/2022 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M394567
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 002) KITCHEN GFCI NOT TR TYPE ART 406.11
RSLV 09/12/2022 09/12/2022 10/18/2022
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002)MASTER BATHROOM MEDICINE CABINET OUTLET NOT GFCI PROTECTED. ART.210.8
RSLV 09/12/2022 09/12/2022 10/18/2022



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Bldg Info Search  |  Electrical Inspection Work Order  |  Back