| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
13 |
$1,625.00 |
| B. Each Additional 10 Floors Or Less |
7 |
$581.00 |
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 018)250.112,118,122 ELEV. RM.(1P15267-1P15272): CAR LIGHT DISC.NOT PROPERLY GND |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |
| |
| 002 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (FLOOR: 018)110.12 ELEV. RM. (1P15267-1P15272): K/OMISSING IN CAR LIGHT DISC. SW. |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |
| |
| 003 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 030)620.23 ELEV. RM.(1P15261-1P15266) : GFCI RECEPTACLEPROVIDED |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (FLOOR: 030)620.53 ELEV. RM. (1P15261-1P15266): NOT PROPER DISC.MEANS FOR CAR LIGHT |
OPEN |
07/01/2019 |
07/01/2019 |
|
| |
| 005 |
(999) |
OTHER (FLOOR: 030)450.11 ELEV. RM.: NO NAME PLATE FOR T-FMR(S) |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |
| |
| 006 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS)450.3, 240.4 NO OCP ON SECONDARY OF T-FMR(S) |
OPEN |
07/01/2019 |
07/01/2019 |
|
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ALL FLOORS)250.30, 450.6 ELEV. RM(S): ALL T-FMR(S) NOT PROPERLYGND |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |
| |
| 008 |
(999) |
OTHER (ALL FLOORS)110.16 NO ARC FLASH WARNING ON NEW EQUIPMENT |
RSLV |
07/01/2019 |
07/01/2019 |
04/12/2022 |