BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M393647
Premises: 135 FULTON STREET MANHATTAN BIN: 1001242     Block: 89   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 139 FULTON ST. Census Tract:   15.01 Health Area:  7700
BSMT, ROOF Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   NASSAU STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 04/20/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/20/2017 10:12 PM
Application Entered:   03/20/2017 Job Start Date:   03/20/2017
Last Change:   04/20/2018 Job End Date:   03/20/2018
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     04/20/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009113 Licensee Name: MARTIN WEINSTEIN
Firm: 000796 Firm Name: JOSEPH WEINSTEIN ELECTRIC
Firm Phone: 718-843-5555  Firm Address: 94-24 88TH STREET CORP OZONE PARK NY 11416 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $100.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSE FAJARDO
Owner Business Name: UNYPO LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF                       
Buildings Total                       
Total Units : 5 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/20/2017 Notice: 1 - FIRST NOTICE 04/03/2018
Power Issued: 03/20/2017 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393647
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/07/2018 02/08/2018 TOR V (30) (2)
INSPECTION COMMENTS: FAIL
 
(2) 04/02/2018 04/03/2018 AYC V R (50) (2)
INSPECTION COMMENTS: FAIL. OBJECTIONS STILL EXIST. REWROTE OBJECTIONS TO MAKE THEM SELF CERTIFIABLE.
 
(3) 04/20/2018 04/20/2018 TSO J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000005857
 
(4) 04/20/2018 04/20/2018 TSO C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000005859

OBJECTION FOR APPLICATION #: M393647
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) T-OUT
RSLV 02/07/2018 02/07/2018 04/02/2018
 
002 (999) OTHER
(ROOF) ARC FLASH LABEL NOT PROVIDED 110.16
RSLV 02/07/2018 02/07/2018 04/02/2018
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS)EMT IN THE CELLAR AND ALUMINUM ON THE ROOF NOT PROPERLY SUPPORTED.ART. 358.30 & 344.30
RSLV 04/02/2018 04/02/2018 04/20/2018
 
004 (999) OTHER
(CELLAR) NO ARC FLASH LABEL ON THE DISCONNECT SWITCH. ART. 110.16
RSLV 04/02/2018 04/02/2018 04/20/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.