Electrical Application Details for App #: M393400
Premises: 560 1 AVENUE MANHATTAN BIN: 1085695     Block: 962   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 560 FIRST AV Census Tract:   62
8TH FLOOR ROOF Admin Area:   M - MANHATTAN Inspection Area:   N
NEW YORK, NY 10016 Community Board:   106
Special Place Name:   NYU LANGONE MEDICAL CENTER
DOB Cross Street(s):   EAST 30 STREET,    EAST 33 STREET
Status:   C - JOB IS SIGNED OFF 10/11/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   03/15/2017 Job Start Date:   03/06/2017
Last Change:   10/11/2018 Job End Date:   01/27/2018
Appointment Status:   
Last Inspection By:   ALGERNON CHARLES       On     10/10/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011240 Licensee Name: CRAIG GILSTON
Firm: 000591 Firm Name: GILSTON ELEC'L CONTNG LLC
Firm Phone: 212-410-7800  Firm Address: 338 EAST 95TH STREET NEW YORK NY 10128 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $4,277.75
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   54384     Submittal #: 17A0120  
Owner / Occup:
Owner Business Name: NYU LANGONE MEDICAL CENTE
Authorized Representative:  RICHARD COHEN
Relationship To Owner:   VICE PRESIDENT OF FACILIT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  2  (2 SETS) 3#1/0
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  28  (2)#350MCM,(15)4#600MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  (1)200A 3P PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008    12  10    20          8075 
Buildings Total 12  10    20               8075 
Total Units : 8121 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/13/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB#4024 NYU LAGONE MEDICAL CENTER SKIRBALL SUPPLEMENTALMITIGATION DESS 8TH FLOOR ROOF

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M393400
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/12/2018 04/13/2018 CBK V (439) (4)
INSPECTION COMMENTS: CONTRACTOR COULD NOT OPEN EQUIPMENT.
 
(2) 10/04/2018 10/04/2018 BMP N (40) (0) Y
INSPECTION COMMENTS: FIRST INSPECTION RAN OVERTIME. BUILDING PERSONNEL WERE ON LUNCH AND I HAD TO LEAVE. NO ACCESS.
 
(3) 10/10/2018 10/10/2018 AYC C R (104) (0)
INSPECTION COMMENTS: PASS.

OBJECTION FOR APPLICATION #: M393400
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) OCPD FOR XMERS NOT PROPERLY LABELED.
RSLV 04/12/2018 04/12/2018 10/10/2018
 
002 (999) OTHER
(BASEMENT) OCP RATING NOT SHOWN ON DEVICES.
RSLV 04/12/2018 04/12/2018 10/10/2018
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ROOF) SIDE BARRIERS ARE MISSING .
RSLV 04/12/2018 04/12/2018 10/10/2018
 
004 (999) OTHER
(ROOF) CONTRACTOR NEED TO VERIFY 3HR. RATING OF WALL.
RSLV 04/12/2018 04/12/2018 10/10/2018